All gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure) and not less than 40 inches (1016 mm) above grade. If the latch handle is located less than 54 inches (1372 mm) from the bottom of the gate, the latch handle shall be located not less than 3 inches (76 mm) below the top of the gate, and neither the gate nor barrier shall have any opening greater than 0.5 inch (12.7 mm) within 18 inches (457 mm) of the latch handle.

Related Code Sections

3109.5.1.7 Special Construction, Gates
gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure) and at least 40 inches ...
3109.4 Special Construction, Public Swimming Pools
All gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure) and at least 40 ...
3109.4 Special Construction, Public Swimming Pools
All gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure ...