Pipe shall be sized to prevent full-bore flow.
713.3.1 Selecting Pipe Wall Roughness
Pipe size calculations shall be conducted with the pipe wall roughness factor (ks), in accordance with the manufacturer's specifications and as modified for aging roughness factors with deposits and corrosion.
713.3.2 Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be designed and installed at slopes in accordance with Table 704.1.