Where more than one ampacity applies for a given circuit length, the lowest value shall be used.
Exception: Where different ampacities apply to portions of a circuit, the higher ampacity shall be permitted to be used if the total portion(s) of the circuit with lower ampacity does not exceed the lesser of 3.0 m (10 ft) or 10 percent of the total circuit.
Informational Note: See 110.14(C) for conductor temperature limitations due to termination provisions.
Upcodes Diagrams

Related Code Sections

(2) Wiring Methods and Materials, Selection of Ampacity
Where more than one calculated or tabulated ampacity could apply for a given circuit length, the lowest value shall be used. Exception: Where ...
430.6 Equipment for General Use, Ampacity and Motor Rating Determination
The size of conductors supplying equipment covered by Article 430 shall be selected from the ampacity tables in accordance with 310.15 or shall ...