1910.333 Selection and Use of Work Practices

Jump To Full Code Chapter
1910.333(a) General
Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.
1910.333(a)(1) Deenergized Parts
Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

Note 1: Examples of increased or additional hazards include interruption of life support equipment, deactivation of emergency alarm systems, shutdown of hazardous location ventilation equipment, or removal of illumination for an area.

Note 2: Examples of work that may be performed on or near energized circuit parts because of infeasibility due to equipment design or operational limitations include testing of electric circuits that can only be performed with the circuit energized and work on circuits that form an integral part of a continuous industrial process in a chemical plant that would otherwise need to be completely shut down in order to permit work on one circuit or piece of equipment.

Note 3: Work on or near deenergized parts is covered by paragraph (b) of this section.
1910.333(a)(2) Energized Parts
If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section.
1910.333(b) Working on or Near Exposed Deenergized Parts
1910.333(b)(1) Application
This paragraph applies to work on exposed deenergized parts or near enough to them to expose the employee to any electrical hazard they present. Conductors and parts of electric equipment that have been deenergized but have not been locked out or tagged in accordance with paragraph (b) of this section shall be treated as energized parts, and paragraph (c) of this section applies to work on or near them.
1910.333(b)(2) Lockout and Tagging
While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been deenergized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph. The requirements shall be followed in the order in which they are presented (i.e., paragraph (b)(2)(i) first, then paragraph (b)(2)(ii), etc.).

Note 1: As used in this section, fixed equipment refers to equipment fastened in place or connected by permanent wiring methods.

Note 2: Lockout and tagging procedures that comply with paragraphs (c) through (f) of 1910.147 will also be deemed to comply with paragraph (b)(2) of this section provided that:

[1] The procedures address the electrical safety hazards covered by this Subpart; and

[2] The procedures also incorporate the requirements of paragraphs (b)(2)(iii)(D) and (b)(2)(iv)(B) of this section.
1910.333(b)(2)(i) Procedures
The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives.

Note: The written procedures may be in the form of a copy of paragraph (b) of this section.
1910.333(b)(2)(iii) Application of Locks and Tags
1910.333(b)(2)(iii)(A)
A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools.
1910.333(b)(2)(iii)(B)
Each tag shall contain a statement prohibiting unauthorized operation of the disconnecting means and removal of the tag.
1910.333(b)(2)(iii)(C)
If a lock cannot be applied, or if the employer can demonstrate that tagging procedures will provide a level of safety equivalent to that obtained by the use of a lock, a tag may be used without a lock.
1910.333(b)(2)(iii)(D)
A tag used without a lock, as permitted by paragraph (b)(2)(iii)(C) of this section, shall be supplemented by at least one additional safety measure that provides a level of safety equivalent to that obtained by use of a lock. Examples of additional safety measures include the removal of an isolating circuit element, blocking of a controlling switch, or opening of an extra disconnecting device.
1910.333(b)(2)(iii)(E)
A lock may be placed without a tag only under the following conditions:
1910.333(b)(2)(iii)(E)(1)
Only one circuit or piece of equipment is deenergized, and
1910.333(b)(2)(iii)(E)(2)
The lockout period does not extend beyond the work shift, and
1910.333(b)(2)(iii)(E)(3)
Employees exposed to the hazards associated with reenergizing the circuit or equipment are familiar with this procedure.
1910.333(b)(2)(iv) Verification of Deenergized Condition
The requirements of this paragraph shall be met before any circuits or equipment can be considered and worked as deenergized.
1910.333(b)(2)(iv)(A)
A qualified person shall operate the equipment operating controls or otherwise verify that the equipment cannot be restarted.
1910.333(b)(2)(iv)(B)
A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test.
1910.333(b)(2)(v) Reenergizing Equipment
These requirements shall be met, in the order given, before circuits or equipment are reenergized, even temporarily.
1910.333(b)(2)(v)(A)
A qualified person shall conduct tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds, and other such devices have been removed, so that the circuits and equipment can be safely energized.
1910.333(b)(2)(v)(B)
Employees exposed to the hazards associated with reenergizing the circuit or equipment shall be warned to stay clear of circuits and equipment.
1910.333(b)(2)(v)(C)
Each lock and tag shall be removed by the employee who applied it or under his or her direct supervision. However, if this employee is absent from the workplace, then the lock or tag may be removed by a qualified person designated to perform this task provided that:
1910.333(b)(2)(v)(C)(1)
The employer ensures that the employee who applied the lock or tag is not available at the workplace, and
1910.333(b)(2)(v)(C)(2)
The employer ensures that the employee is aware that the lock or tag has been removed before he or she resumes work at that workplace.
1910.333(b)(2)(v)(D)
There shall be a visual determination that all employees are clear of the circuits and equipment.
1910.333(b)(2)(ii) Deenergizing Equipment
1910.333(b)(2)(ii)(A)
Safe procedures for deenergizing circuits and equipment shall be determined before circuits or equipment are deenergized.
1910.333(b)(2)(ii)(B)
The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.
1910.333(b)(2)(ii)(C)
Stored electric energy which might endanger personnel shall be released. Capacitors shall be discharged and high capacitance elements shall be short-circuited and grounded, if the stored electric energy might endanger personnel.

Note: If the capacitors or associated equipment are handled in meeting this requirement, they shall be treated as energized.
1910.333(b)(2)(ii)(D)
Stored non-electrical energy in devices that could reenergize electric circuit parts shall be blocked or relieved to the extent that the circuit parts could not be accidentally energized by the device.
1910.333(c) Working on or Near Exposed Energized Parts
1910.333(c)(1) Application
This paragraph applies to work performed on exposed live parts (involving either direct contact or by means of tools or materials) or near enough to them for employees to be exposed to any hazard they present.
1910.333(c)(2) Work on Energized Equipment
Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.
1910.333(c)(3) Overhead Lines
if work is to be performed near overhead lines, the lines shall be deenergized and grounded, or other protective measures shall be provided before work is started. If the lines are to be deenergized, arrangements shall be made with the person or organization that operates or controls the electric circuits involved to deenergize and ground them. If protective measures, such as guarding, isolating, or insulating, are provided, these precautions shall prevent employees from contacting such lines directly with any part of their body or indirectly through conductive materials, tools, or equipment.

Note: The work practices used by qualified persons installing insulating devices on overhead power transmission or distribution lines are covered by 1910.269 of this Part, not by 1910.332 through 1910.335 of this Part. Under paragraph (c)(2) of this section, unqualified persons are prohibited from performing this type of work.
1910.333(c)(3)(i) Unqualified Persons
1910.333(c)(3)(i)(A)
When an unqualified person is working in an elevated position near overhead lines, the location shall be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line than the following distances:
1910.333(c)(3)(i)(A)(1)
For voltages to ground 50kV or below - 10 feet (305 cm);
1910.333(c)(3)(i)(A)(2)
For voltages to ground over 50kV - 10 feet (305 cm) plus 4 inches (10 cm) for every 10kV over 50kV.
1910.333(c)(3)(i)(B)
When an unqualified person is working on the ground in the vicinity of overhead lines, the person may not bring any conductive object closer to unguarded, energized overhead lines than the distances given in paragraph (c)(3)(i)(A) of this section.

Note: For voltages normally encountered with overhead power line, objects which do not have an insulating rating for the voltage involved are considered to be conductive.
1910.333(c)(3)(iii) Vehicular and Mechanical Equipment
1910.333(c)(3)(iii)(A)
Any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines shall be operated so that a clearance of 10 ft. (305 cm) is maintained. If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10kV over that voltage. However, under any of the following conditions, the clearance may be reduced:
1910.333(c)(3)(iii)(A)(1)
If the vehicle is in transit with its structure lowered, the clearance may be reduced to 4 ft. (122 cm). If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10 kV over that voltage.
1910.333(c)(3)(iii)(A)(2)
If insulating barriers are installed to prevent contact with the lines, and if the barriers are rated for the voltage of the line being guarded and are not a part of or an attachment to the vehicle or its raised structure, the clearance may be reduced to a distance within the designed working dimensions of the insulating barrier.
1910.333(c)(3)(iii)(A)(3)
If the equipment is an aerial lift insulated for the voltage involved, and if the work is performed by a qualified person, the clearance (between the uninsulated portion of the aerial lift and the power line) may be reduced to the distance given in Table S-5.
1910.333(c)(3)(iii)(B)
Employees standing on the ground may not contact the vehicle or mechanical equipment or any of its attachments, unless:
1910.333(c)(3)(iii)(B)(1)
The employee is using protective equipment rated for the voltage; or
1910.333(c)(3)(iii)(B)(2)
The equipment is located so that no uninsulated part of its structure (that portion of the structure that provides a conductive path to employees on the ground) can come closer to the line than permitted in paragraph (c)(3)(iii) of this section.
1910.333(c)(3)(iii)(C)
If any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines is intentionally grounded, employees working on the ground near the point of grounding may not stand at the grounding location whenever there is a possibility of overhead line contact. Additional precautions, such as the use of barricades or insulation, shall be taken to protect employees from hazardous ground potentials, depending on earth resistivity and fault currents, which can develop within the first few feet or more outward from the grounding point.
1910.333(c)(3)(ii) Qualified Persons
When a qualified person is working in the vicinity of overhead lines, whether in an elevated position or on the ground, the person may not approach or take any conductive object without an approved insulating handle closer to exposed energized parts than shown in Table S-5 unless:
1910.333(c)(3)(ii)(A)
The person is insulated from the energized part (gloves, with sleeves if necessary, rated for the voltage involved are considered to be insulation of the person from the energized part on which work is performed), or
1910.333(c)(3)(ii)(B)
The energized part is insulated both from all other conductive objects at a different potential and from the person, or
See More

Related Code Sections

1910.333 Electrical, Selection and Use of Work Practices
safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall ...
1910.333(c)(2) Electrical, Work on Energized Equipment
) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary ...
1910.333(b)(2) Electrical, Lockout and Tagging
in which they are presented (i.e., paragraph (b)(2)(i) first, then paragraph (b)(2)(ii), etc.). Note 1: As used in this section, fixed equipment ...
1910.333(c)(7) Electrical, Portable Ladders
Portable ladders shall have nonconductive siderails if they are used where the employee or the ladder could contact exposed energized parts ...
1910.333(c)(5) Electrical, Confined or Enclosed Work Spaces
When an employee works in a confined or enclosed space (such as a manhole or vault) that contains exposed energized parts, the employer shall provide ...