1910.157(d)(1)
Portable fire extinguishers shall be provided for employee use and selected and distributed based on the classes of anticipated workplace fires and on the size and degree of hazard which would affect their use.
1910.157(d)(2)
The employer shall distribute portable fire extinguishers for use by employees on Class A fires so that the travel distance for employees to any extinguisher is 75 feet (22.9 m) or less.
1910.157(d)(3)
The employer may use uniformly spaced standpipe systems or hose stations connected to a sprinkler system installed for emergency use by employees instead of Class A portable fire extinguishers, provided that such systems meet the respective requirements of 1910.158 or 1910.159, that they provide total coverage of the area to be protected, and that employees are trained at least annually in their use.
1910.157(d)(4)
The employer shall distribute portable fire extinguishers for use by employees on Class B fires so that the travel distance from the Class B hazard area to any extinguisher is 50 feet (15.2 m) or less.
1910.157(d)(5)
The employer shall distribute portable fire extinguishers used for Class C hazards on the basis of the appropriate pattern for the existing Class A or Class B hazards.
1910.157(d)(6)
The employer shall distribute portable fire extinguishers or other containers of Class D extinguishing agent for use by employees so that the travel distance from the combustible metal working area to any extinguishing agent is 75 feet (22.9 m) or less. Portable fire extinguishers for Class D hazards are required in those combustible metal working areas where combustible metal powders, flakes, shavings, or similarly sized products are generated at least once every two weeks.
Upcodes Diagrams

Related Code Sections

1910.157(d) Fire Protection, Selection and Distribution
Portable fire extinguishers shall be provided for employee use and selected and distributed based on the classes of anticipated workplace fires ...
1910.157(d)(6) Fire Protection,
The employer shall distribute portable fire extinguishers or other containers of Class D extinguishing agent for use by employees so that the travel ...
1910.1048(h)(1) Toxic and Hazardous Substances, Selection
The employer shall select protective clothing and equipment based upon the form of formaldehyde to be encountered, the conditions of use ...
1910.252(b)(2)(i) Welding, Cutting, and Brazing, Selection
Helmets or hand shields shall be used during all arc welding or arc cutting operations, excluding submerged arc welding. Helpers or attendants shall ...