// CODE SNIPPET
1810.3.8.2.2 Seismic Reinforcement in Seismic Design Categories C Through F
Go To Full Code Chapter
For structures assigned to Seismic Design Category C, D, E or F, precast nonprestressed piles shall be reinforced as specified in this section. The minimum longitudinal reinforcement ratio shall be 0.01 throughout the length. Transverse reinforcement shall consist of closed ties or spirals with a minimum 3/8 inch (9.5 mm) diameter. Spacing of transverse reinforcement shall not exceed the smaller of eight times the diameter of the smallest longitudinal bar or 6 inches (152 mm) within a distance of three times the least pile dimension from the bottom of the pile cap. Spacing of transverse reinforcement shall not exceed 6 inches (152 mm) throughout the remainder of the pile.
Upcodes Diagrams
Related Code Sections
1810.3.8.2.2 Soils and Foundations, Seismic Reinforcement in Seismic Design Categories C Through F
For structures assigned to Seismic Design Category C, D, E or F, precast nonprestressed piles shall be reinforced as specified in this section. The ...
2111.4 Masonry, Seismic Reinforcement
In structures assigned to Seismic Design Category A or B, seismic reinforcement is not required. In structures assigned to Seismic Design Category C ...
2111.4 Masonry, Seismic Reinforcement
In structures assigned to Seismic Design Category A or B, seismic reinforcement is not required. In structures assigned to Seismic Design Category C ...
2113.3 Masonry, Seismic Reinforcement
In structures assigned to Seismic Design Category A or B, seismic reinforcement is not required. In structures assigned to Seismic Design Category C ...
2113.3 Masonry, Seismic Reinforcement
In structures assigned to Seismic Design Category A or B, seismic reinforcement is not required. In structures assigned to Seismic Design Category C ...