When a change of occupancy results in a structure being reclassified to a higher risk category, the structure shall conform to the seismic requirements for a new structure of the higher risk category.
Exceptions:
  1. Specific seismic detailing requirements of Section 1613 for a new structure shall not be required to be met where the seismic performance is shown to be equivalent to that of a new structure. A demonstration of equivalence shall consider the regularity, overstrength, redundancy and ductility of the structure.
  2. When a change of use results in a structure being reclassified from Risk Category I or II to Risk Category III and the structure is located where the seismic coefficient, SDS, is less than 0.33, compliance with the seismic requirements of Section 1613 are not required.

Related Code Sections

3408.4 Existing Buildings and Structures, Seismic
When a change of occupancy results in a structure being reclassified to a higher risk category, the structure shall conform to the seismic ...
1006.3 Change of Occupancy, Seismic Loads
1613 of the International Building Code for the new risk category using full seismic forces. Exceptions: Where a change of use results in a building ...
1007.3 Change of Occupancy, Seismic Loads
Existing buildings with a change of occupancy shall comply with the seismic provisions of Sections 1007.3.1 and 1007.3.2 ...
1302.4 Relocated or Moved Buildings, Seismic Loads
Buildings shall comply with International Building Code or International Residential Code seismic provisions at the new location as applicable ...
1402.4 Relocated or Moved Buildings, Seismic Loads
Buildings shall comply with International Building Code or International Residential Code seismic provisions at the new location as applicable ...