1010.5.2 Security Access Turnstiles
JUMP TO FULL CODE CHAPTER
Security access turnstiles that inhibit travel in the direction of egress utilizing a physical barrier shall be permitted to be considered as a component of the means of egress, provided that all of the following criteria are met:
- The building is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 903.3.1.1.
- Each security access turnstile lane configuration has a minimum clear passage width of 22 inches (559 mm).
- Any security access turnstile lane configuration providing a clear passage width of less than 32 inches (810 mm) shall be credited with a maximum egress capacity of 50 persons.
- Any security access turnstile lane configuration providing a clear passage width of 32 inches (810 mm) or more shall be credited with a maximum egress capacity as calculated in accordance with Section 1005.
- Each secured physical barrier shall automatically retract or swing to an unobstructed open position in the direction of egress, under each of the following conditions:5.1. Upon loss of power to the turnstile or any part of the access control system that secures the physical barrier.5.2. Upon actuation of a clearly identified manual release device with ready access that results in direct interruption of power to each secured physical barrier, after which such barriers remain in the open position for not less than 30 seconds. The manual release device shall be positioned at one of the following locations:5.3. Upon actuation of the building fire alarm system, if provided, after which the physical barrier remains in the open position until the fire alarm system is manually reset.Exception: Actuation of a manual fire alarm box.5.4. Upon actuation of the building automatic sprinkler system or fire detection system, after which the physical barrier remains in the open position until the fire alarm system is manually reset.
Related Code Sections
1010.3.2 Means of Egress, Security Access Turnstiles
Security access turnstiles that inhibit travel in the direction of egress utilizing a physical barrier shall be permitted to be considered ...
Building Code 2018 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.3 Turnstiles and Similar Devices > 1010.3.2 Security Access Turnstiles
1010.5.2 Means of Egress, Security Access Turnstiles
Security access turnstiles that inhibit travel in the direction of egress utilizing a physical barrier shall be permitted to be considered ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.5 Turnstiles and Similar Devices > 1010.5.2 Security Access Turnstiles
1010.5.4 Means of Egress, Additional Door
1010.1 within 50 feet (15 240 mm). Exception: A side-hinged swinging door is not required at security access turnstiles that comply with Section ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.5 Turnstiles and Similar Devices > 1010.5.4 Additional Door
Section 1010 Means of Egress, Doors, Gates and Turnstiles
Security access turnstiles that inhibit travel in the direction of egress utilizing a physical barrier shall be permitted ...
Section 1010 Means of Egress, Doors, Gates and Turnstiles
Security access turnstiles that inhibit travel in the direction of egress utilizing a physical barrier shall be permitted ...