// CODE SNIPPET
(F) Securing in Place
Go To Full Code Chapter
Power cables; communications cables, connecting cables, interconnecting cables, and associated boxes, connectors, plugs, and receptacles that are listed as part of, or for, information technology equipment shall not be required to be secured in place where installed under raised floors.
Informational Note: Securement requirements for raceways and cables not listed as part of, or for, information technology equipment are found in 300.11.
Related Code Sections
(A) Wiring Methods and Materials, Secured in Place
Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place ...
(A) Wiring Methods and Materials, Secured in Place
Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place ...
(B) Equipment for General Use, Secured in Place
Cables shall be secured in place by nonmetallic frames or spreaders or other approved means while the concrete or other finish is applied ...
(B) Equipment for General Use, Secured in Place
Cables shall be secured in place by nonmetallic frames or spreaders or other approved means while the concrete or other finish is applied ...
(F) Special Equipment, Securing in Place
that are listed as part of, or for, information technology equipment shall not be required to be secured in place where installed under raised floors ...