63.3.1.9.5 Securing Compressed Gas Containers, Cylinders, and Tanks
Go To Full Code Chapter
Compressed gas containers, cylinders, and tanks in use or in storage shall be secured to prevent them from falling or being knocked over by corralling them and securing them to a cart, framework, or fixed object by use of a restraint, unless otherwise permitted by 63.3.1.9.5.1 and 63.3.1.9.5.2. [55:7.1.9.4]
63.3.1.9.5.1
Compressed gas containers, cylinders, and tanks in the process of examination, servicing, and refilling shall not be required to be secured. [55:7.1.9.4.1]
63.3.1.9.5.2
At cylinder-filling plants, authorized cylinder requalifier's facilities, and distributors' warehouses, the nesting of cylinders shall be permitted as a means to secure cylinders. [55:7.1.9.4.2]
Related Code Sections
63.3.1.9.5 Compressed Gases and Cryogenic Fluids, Securing Compressed Gas Containers, Cylinders, and Tanks
Compressed gas containers, cylinders, and tanks in use or in storage shall be secured to prevent them from falling or being knocked over ...
703.5 Gaseous Hydrogen Systems, Security
Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement in accordance with Chapter 53 ...
63.3.3 Compressed Gases and Cryogenic Fluids, Use and Handling
The use and handling of compressed gas cylinders, containers, tanks, and systems shall be in accordance with 63.3.3.1. [55:7.3.1.1 ...
63.3.1 Compressed Gases and Cryogenic Fluids, General
] Compressed gas cylinders, containers, and tanks used for metal hydride storage systems shall be designed ...
63.3.3.1 Compressed Gases and Cryogenic Fluids, General
The use and handling of compressed gas cylinders, containers, tanks, and systems shall be in accordance with 63.3.3.1. [55:7.3.1.1 ...