404.3.2 Secondary-Recirculation Systems
JUMP TO FULL CODE CHAPTER
For secondary-recirculation systems where the supply air or a portion thereof to each ventilation zone is recirculated air (air that has not been directly mixed with outdoor air) from other zones, zone ventilation efficiency (Evz) shall be determined in accordance with Equation 404.3.2(1). Examples of secondary-recirculation systems include dual-fan dual-duct and fan-powered mixing-box systems, and systems that include transfer fans for conference rooms.
Evz = (Fa+Xs•Fb-Zpz•Ep•Fc)/Fa [Equation 404.3.2(1)]
The system air fractions Fa, Fb, and Fc shall be determined in accordance with Equation 404.3.2(2), Equation 404.3.2(3), and Equation 404.3.2(4). The zone primary air fraction (Ep) shall be determined in accordance with Equation 404.3.2(5). For single-zone and single-supply systems Ep shall equal to 1.0. The zone secondary recirculation fraction (Er) shall be determined by the designer based on system configuration. The zone air distribution effectiveness (Ez) shall be determined in accordance with Section 403.2.2. [ASHRAE 62.1:A1.2.2]

Where:
Ep - Primary air fraction: The fraction of primary air in the discharge air to the ventilation zone.
Er - Secondary recirculation fraction: In systems with secondary recirculation of return air, the fraction of secondary recirculated air to the zone that is representative of average system return air rather than air directly recirculated from the zone.
Evz - Zone ventilation efficiency: The efficiency with which the system distributes air from the outdoor air intake to the breathing zone in any particular ventilation zone.
Ez - Zone air distribution effectiveness: A measure of the effectiveness of supply air distribution to the breathing zone. Ez is determined in accordance with Section 403.2.2.
Fa - Supply air fraction: The fraction of supply air to the ventilation zone from sources or air outside the zone.
Fb - Mixed air fraction: The fraction of supply air to the ventilation zone from fully mixed primary air.
Fc - Outdoor air fraction: The fraction of outdoor air to the ventilation zone from sources of air outside the zone.
Vdz - Zone discharge airflow: The expected discharge (supply) airflow to the zone that includes primary airflow and secondary recirculated airflow, cfm (m3/min).
Vpz - Zone primary airflow: Determine in accordance with Section 403.5.1.
Xs - Average outdoor air fraction: At the primary air handler, the fraction of outdoor air intake flow in the system primary airflow.
Zpz - Primary outdoor air fraction: The outdoor air fraction required in the primary air supplied to the ventilation zone prior to the introduction of secondary recirculation air. [ASHRAE 62.1:A3]
Related Code Sections
404.3.2 Ventilation Air, Secondary-Recirculation Systems
For secondary-recirculation systems where the supply air or a portion thereof to each ventilation zone is recirculated air (air that has not been ...
Uniform Mechanical Code 2018 of Nevada > 4 Ventilation Air > 404.0 Multiple-Zone Systems > 404.3 Zone Ventilation Efficiency > 404.3.2 Secondary-Recirculation Systems
516.2.2 Exhaust Systems, Recirculation
Recirculating systems shall be listed with a testing laboratory in accordance with UL 710B or equivalent. [NFPA 96:13.2.4] ...
Uniform Mechanical Code 2018 of Nevada > 5 Exhaust Systems > 516.0 Recirculating Systems > 516.2 Design Restrictions > 516.2.2 Recirculation
(8) Special Equipment, Signs in Fountains
for the fountain recirculating system. The bonding connection shall be as near as practicable to the fountain and shall be permitted to be made to metal ...
National Electrical Code 2017 of Nevada > 6 Special Equipment > 600 Electric Signs and Outline Lighting > 600.7 Grounding and Bonding > (B) Bonding > (8) Signs in Fountains
L 501.3 Sustainable Practices, Recirculation Systems
Recirculation systems shall comply with Section L 501.3.1 and Section L 501.3.2 ...
Uniform Plumbing Code 2018 of Nevada > L Sustainable Practices > L 501.0 Water Heating Design, Equipment, and Installation > L 501.3 Recirculation Systems
L 502.3 Sustainable Practices, Recirculation Systems
Recirculation systems shall comply with the provisions of Section L 501.3 ...
Uniform Plumbing Code 2018 of Nevada > L Sustainable Practices > L 502.0 Service Hot Water — Low-Rise Residential Buildings > L 502.3 Recirculation Systems