54.3.2.1
Secondary containment, such as double-walled piping or exhausted enclosures, shall be provided for piping, valves, fittings, and related components, unless otherwise permitted by 54.3.2.3.
54.3.2.2
Secondary containment shall be capable of directing a sudden release to an approved treatment system.
54.3.2.3
Secondary containment shall not be required for welded stainless steel piping and tubing.