610.1 General
Seats in bathtubs and shower compartments shall comply with 610.
610.2 Bathtub Seats
The top of bathtub seats shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum above the bathroom finish floor.  The depth of a removable in-tub seat shall be 15 inches (380 mm) minimum and 16 inches (405 mm) maximum.  The seat shall be capable of secure placement.  Permanent seats at the head end of the bathtub shall be 15 inches (380 mm) deep minimum and shall extend from the back wall to or beyond the outer edge of the bathtub.
Figure 610.2 Bathtub Seats
Figure (a) shows a removable in-tub seat in elevation and plan views that is 15 to 16 inches (380 to 405 mm) deep and 17 to 19 inches (430 to 485 mm) above the floor measured to the top of the seat.  Figure (b) shows permanent tub seat in elevation and plan views that is 15 inches (380 mm) minimum deep and 17 to 19 inches (430 to 485 mm) above the floor measured to the top of the seat.
610.3 Shower Compartment Seats
Where a seat is provided in a standard roll-in shower compartment, it shall be a folding type, shall be installed on the side wall adjacent to the controls, and shall extend from the back wall to a point within 3 inches (75 mm) of the compartment entry.  Where a seat is provided in an alternate roll-in type shower compartment, it shall be a folding type, shall be installed on the front wall opposite the back wall, and shall extend from the adjacent side wall to a point within 3 inches (75 mm) of the compartment entry.  In transfer-type showers, the seat shall extend from the back wall to a point within 3 inches (75 mm) of the compartment entry.  The top of the seat shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum above the bathroom finish floor.  Seats shall comply with 610.3.1 or 610.3.2.
Figure 610.3 Extent of Seat
Figure (a) is a plan view of a rectangular seat and figure (b) is a plan view of an L-shaped seat.  The front edge of each is 3 inches (75 mm) maximum from the compartment entry.
610.3.1 Rectangular Seats
The rear edge of a rectangular seat shall be 21/2 inches (64 mm) maximum and the front edge 15 inches (380 mm) minimum and 16 inches (405 mm) maximum from the seat wall.  The side edge of the seat shall be 11/2 inches (38 mm) maximum from the adjacent wall.
Figure 610.3.1 Rectangular Shower Seat
610.3.2 L-Shaped Seats
The rear edge of an L-shaped seat shall be 21/2 inches (64 mm) maximum and the front edge 15 inches (380 mm) minimum and 16 inches (405 mm) maximum from the seat wall.  The rear edge of the "L" portion of the seat shall be 11/2 inches (38 mm) maximum from the wall and the front edge shall be 14 inches (355 mm) minimum and 15 inches (380 mm) maximum from the wall.  The end of the "L" shall be 22 inches (560 mm) minimum and 23 inches maximum (585 mm) from the main seat wall.
Figure 610.3.2 L-Shaped Shower Seat
610.4 Structural Strength
Allowable stresses shall not be exceeded for materials used when a vertical or horizontal force of 250 pounds (1112 N) is applied at any point on the seat, fastener, mounting device, or supporting structure.

Related Code Sections

604.4 Plumbing Elements and Facilities, Seats
The seat height of a water closet above the finish floor shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum measured to the top ...
607.3 Plumbing Elements and Facilities, Seat
A permanent seat at the head end of the bathtub or a removable in-tub seat shall be provided.  Seats shall comply with 610 ...
608.4 Plumbing Elements and Facilities, Seats
A folding or non-folding seat shall be provided in transfer type shower compartments. A folding seat shall be provided in roll-in type showers ...
610 Plumbing Elements and Facilities, Seats
Seats in bathtubs and shower compartments shall comply with 610 ...
1002.4.7 Recreation Facilities, Companion Seats
Where the interior width of the amusement ride is greater than 53 inches (1345 mm), seating is provided for more than one rider, and the wheelchair ...