Ducts, air handlers and filter boxes shall be sealed. Joints and seams shall comply with Section M1601.4.1.
N1103.3.2.1 (R403.3.2.1) Sealed Air Handler
Air handlers shall have a manufacturer's designation for an air leakage of not greater than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193.

Related Code Sections

R403.3.2 [RE] Residential Energy Efficiency, Sealing (Mandatory)
Ducts, air handlers and filter boxes shall be sealed. Joints and seams shall comply with either the International Mechanical Code or International ...
R403.3.2 Foundations, Protection of Horizontal Insulation Below Ground
Horizontal insulation placed less than 12 inches (305 mm) below the ground surface or that portion of horizontal insulation extending outward more ...
R402.4 [RE] Residential Energy Efficiency, Air Leakage (Mandatory)
with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction ...