E303.3.1 Sealants
2020 FBC - Building, 7th edition > E Florida Standard for Radon-Resistant New Commercial Construction > E301 Construction Requirements Forpassive Controls > E303 Concrete Floors in Contact With Soil Gas > E303.3 Sealing of Construction Joints, Penetrations, Cracks, and Other Connections > E303.3.1 Sealants
Go To Full Code Chapter
Sealants shall be selected and installed in compliance with ASTM C920, Standard Specification for Elastomeric Joint Sealants, and ASTM C 1193, Standard Guide for Use of Joint Sealants.
- Sealant materials shall be compatible with the materials they join, including curing compounds and admixtures, and with materials that will be applied over them, including floor finishing materials.
- Field-molded sealants shall be installed in sealant reservoirs proportioned, cleaned of laitance and prepared in accordance with the manufacturer's recommendations. For elastomeric sealants, this generally requires the installation of a bond breaker or backer rod.
- When the installed sealant is not protected by a finished floor or other protective surface, it shall be suitable to withstand the traffic to which it will be exposed.
- Waterstops shall be preformed from polyvinyl chloride or other noncorrosive material and shall be selected and installed in compliance with ACI 504R
Related Code Sections
C405.1 Florida Standard for Mitigation of Radon in Existing Buildings, Sealants
Acceptable caulks and sealants shall conform with Standard Specifications for Elastomeric Joint Sealants, and ASTM C962, Standard Guide for Use ...
C405.1 Florida Standard for Mitigation of Radon in Existing Buildings, Sealants
Acceptable caulks and sealants shall conform with Standard Specifications for Elastomeric Joint Sealants, and ASTM C962, Standard Guide for Use ...
E303.3.1 Florida Standard for Radon-Resistant New Commercial Construction, Sealants
Sealants shall be selected and installed in compliance with ASTM C920, Standard Specification for Elastomeric Joint Sealants, and ASTM C 1193 ...
2020 FBC - Building, 7th edition > E Florida Standard for Radon-Resistant New Commercial Construction > E301 Construction Requirements Forpassive Controls > E303 Concrete Floors in Contact With Soil Gas > E303.3 Sealing of Construction Joints, Penetrations, Cracks, and Other Connections > E303.3.1 Sealants
E303.3.1 Florida Standard for Radon-Resistant New Commercial Construction, Sealants
Sealants shall be selected and installed in compliance with ASTM C920, Standard Specification for Elastomeric Joint Sealants, and ASTM C 1193 ...
E405.1 Florida Standard for Mitigation of Radon in Existing Buildings Effective: June 1, 1994, Sealants
Acceptable caulks and sealants shall conform with ASTM C920, Standard Specifications for Elastomeric Joint Sealants, and ASTM C962, Standard Guide ...