// CODE SNIPPET
1106.7 Scupper Sizing
Go To Full Code Chapter
Scuppers shall be sized in accordance with Table 1106.7.
TABLE 1106.7
SIZING SCUPPERS FOR A-5 INCH PER HOUR RATE OF RAINFALL
SIZING SCUPPERS FOR A-5 INCH PER HOUR RATE OF RAINFALL
HEAD IN INCHES | HORIZONTALLY PROJECTED ROOF AREA (SQUARE FEET) | ||||||
LENGTH OF WEIR IN INCHES | |||||||
4 | 6 | 8 | 12 | 16 | 20 | 24 | |
1 | 230 | 346 | 461 | 692 | 923 | 1153 | 1384 |
2 | 641 | 961 | 1282 | 1923 | 2564 | 3205 | 3846 |
3 | 1153 | 1730 | 2307 | 3461 | 4615 | 5769 | 6923 |
4 | 1794 | 2692 | 3589 | 5384 | 7179 | 8974 | 10,769 |
Note:
To adjust this table for other than a 5-inch design rain fall rate, multiply the square footage on the table by 5 then divide by the local design rain fall rate.
Example:
For 4 inches of design rainfall rate, a 4-inch long scupper with a 1-inch head would accommodate 287 square feet. (230 x 5) ÷4 = 287.
Upcodes Diagrams
Related Code Sections
1106.7 Storm Drainage, Scupper Sizing
Scuppers shall be sized in accordance with Table 1106.7. TABLE 1106.7 SIZING SCUPPERS FOR A-5 INCH PER HOUR RATE OF RAINFALL HEAD IN ...
1514.4.2 Roof Assemblies and Rooftop Structures, Overflow Drains and Scuppers
Where roof drains are required, overflow drains or overflow scuppers sized in accordance with Florida Building Code, Plumbing and ASCE 7, Chapter 8 ...
1108.3 Storm Drainage, Sizing of Secondary Drains
is sized. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7 ...
1514.4.2 Roof Assemblies and Rooftop Structures, Overflow Drains and Scuppers
Where roof drains are required, overflow drains or overflow scuppers sized in accordance with Florida Building Code, Plumbing shall be installed ...
1514.4.2 Roof Assemblies and Rooftop Structures, Overflow Drains and Scuppers
Where roof drains are required, overflow drains or overflow scuppers sized in accordance with Florida Building Code, Plumbing shall be installed ...