1001.2 Scope; Boilers; Labor and Industry
Go To Full Code Chapter
Anyone who installs
a boiler must ensure that the boiler is inspected by the
Department of Labor and Industry after installation is complete
and before the boiler is placed in operation if the individual or
combined Btu input exceeds:
- 100,000 Btu/hr for steam boilers;
- 500,000 Btu/hr for hot water supply boilers; or
- 750,000 Btu/hr for hot water heating boilers.
Exceptions: Boilers identified in Minnesota Statutes, section
326.B.988, including the following, are not subject to this
section:
- Boilers in buildings occupied solely for residential purposes with accommodations for not more than five families.
- Boilers under the direct jurisdiction of the United States.
- Boilers located on farms used solely for agricultural or horticultural purposes; for the purposes of this subpart, boilers used for mint oil extraction are considered used for agricultural or horticultural purposes, provided that the owner or lessee complies with the inspection requirements contained in Minnesota Statutes, Section 326B.958.
Upcodes Diagrams
Related Code Sections
1001.2 Boilers, Water Heaters and Pressure Vessels, Scope; Boilers; Labor and Industry
Anyone who installs
a boiler must ensure that the boiler is inspected by the
Department of Labor and Industry after installation is complete ...
425.1 Equipment for General Use, Scope
This article covers fixed industrial process heating employing electric resistance or electrode heating technology. For the purpose of this article ...
MN Department of Labor and Industry
Additional information on the Minnesota State Building Code can be found at the Minnesota Department of Labor & Industry's website: http ...
Section 1 Fires or Barbecues on Balconies or Patios, Open Flame and Fuel Storage Prohibited
change and is available at the office of the commissioner of the Department of Labor and Industry and at the State Law Library, 25 Rev. Dr. Martin ...
Chapter 1 Scope and Administration
and is available at the office of the commissioner of the Department of Labor and Industry and at the State Law Library, 25 Rev. Dr. Martin Luther ...