The calculation of a feeder or service load for schools shall be permitted in accordance with Table 220.86 in lieu of Part III of this article where equipped with electric space-heating, air conditioning, or both. The connected load to which the demand factors of Table 220.86 apply shall include all of the interior and exterior lighting, power, water heating, cooking, other loads, and the larger of the air-conditioning load or space-heating load within the building or structure.
Feeders and service conductors whose calculated load is determined by this optional calculation shall be permitted to have the neutral load determined by 220.61. Where the building or structure load is calculated by this optional method, feeders within the building or structure shall have ampacity as permitted in Part III of this article; however, the ampacity of an individual feeder shall not be required to be larger than the ampacity for the entire building.
This section shall not apply to portable classroom buildings.
Table 220.86 Optional Method — Demand Factors for Feeders and Service Conductors for Schools
Connected Load Demand Factor (Percent)
First 33 VA/m2 Plus, (3 VA/ft2) at 100
Over 33 through 220 VA/m2 Plus, (3 through 20 VA/ft2) at 75
Remainder over 220 VA/m2 (20 VA/ft2) at 25
Upcodes Diagrams

Related Code Sections

220.86 Wiring and Protection, Schools
The calculation of a feeder or service load for schools shall be permitted in accordance with Table 220.86 in lieu of Part III of this article where ...
220.86 Wiring and Protection, Schools
The calculation of a feeder or service load for schools shall be permitted in accordance with Table 220.86 in lieu of Part III of this article where ...
915.2.3 Fire Protection and Life Safety Systems, Group E Occupancies
to an on-site location that is staffed by school personnel. Exception: Carbon monoxide alarm signals shall not be required to be automatically ...
915.2.3 Fire Protection and Life Safety Systems, Group E Occupancies
to an on-site location that is staffed by school personnel. Exception: Carbon monoxide alarm signals shall not be required to be automatically ...
109.1 Application and Administration, Storm Shelters Requiring Peer Review
Storm shelters in elementary schools, secondary schools and day care facilities with a design occupant capacity greater than 16. Storm shelters ...