The following materials, or any combination of them shall be considered as generally satisfactory bearing materials; hard sound, medium hard, intermediate, and soft rock; hardpan; granular soils of G and S groups; dense or medium silt soils of groups ML and MH; and hard or medium clay soils of groups CL and CH.

TABLE 11-1
UNIFIED SOIL CLASSIFICATION


FIELD IDENTIFICATION PROCEDURES FOR FINE-GRAINED SOILS OR FRACTIONS (Notes for Table 11-1)

These procedures are to be performed on the minus No. 40 sieve size particles, approximately 1/64 in. For field classification purposes, screening is not intended, simply remove by hand the coarse particles that interfere with the tests.

Dilatancy (reaction to shaking)

After removing particles larger than No. 40 sieve size, prepare a pat of moist soil with a volume of about one-half cubic inch. Add enough water if necessary to make the soil soft but not sticky.

Place the pat in the open palm of one hand and shake horizontally, striking vigorously against the other hand several times. A positive reaction consists of the appearance of water on the surface of the pat which changes to a livery consistency and becomes glossy. When the sample is squeezed between the fingers, the water and gloss disappear from the surface, the pat stiffens, and finally it cracks or crumbles. The rapidity of appearance of water during shaking and of its disappearance during squeezing assist in identifying the character of the fines in a soil.

Very fine clean sands give the quickest and most distinct reaction whereas a plastic clay has no reaction. Inorganic silts, such as a typical rock flour, show a moderately quick reaction.

Dry Strength (crushing characteristics)

After removing particles larger than No. 40 sieve size, mold a pat of soil to the consistency of putty, adding water if necessary. Allow the pat to dry completely by oven, sun or air-drying, and then test its strength by breaking and crumbling between the fingers. This strength is a measure of the character and quantity of the colloidal fraction contained in the soil. The dry strength increases with increasing plasticity.

High dry strength is characteristic for clays of the CH group. A typical inorganic silt possesses only very slight dry strength. Silty fine sands and silts have about the same slight dry strength, but can be distinguished by the feel when powdering the dried specimen. Fine sand feels gritty whereas a typical silt has the smooth feel of flour.

Toughness (consistency near plastic limit)

After particles larger than the No. 40 sieve size are removed, a specimen of soil about one-half inch cube in size, is molded to the consistency of putty. If too dry, water must be added and if sticky, the specimen should be spread out in a thin layer and allowed to lose some moisture by evaporation. Then the specimen is rolled out by hand on a smooth surface or between the palms into a thread about one-eighth inch in diameter. The thread is then folded and rerolled repeatedly. During this manipulation, the moisture content is gradually reduced and the specimen stiffens, finally loses its plasticity, and crumbles when the plastic limit is reached.

After the thread crumbles, the pieces should be lumped together and a slight kneading action continued until the lump crumbles. The tougher the thread near the plastic limit and the stiffer the lump when it finally crumbles, the more potent is the colloidal clay fraction in the soil. Weakness of the thread at the plastic limit and quick loss of coherence of the lump below the plastic limit indicate either inorganic clay of low plasticity, or materials such as kaolin-type clays and organic clays which occur below the A-line.

Highly organic clays have a very weak and spongy feel at the plastic limit.
Upcodes Diagrams

Related Code Sections

§27-676 Foundations, Satisfactory Bearing Material
The following materials, or any combination of them shall be considered as generally satisfactory bearing materials; hard sound, medium hard ...
Article 8 Materials, Loads and Stresses [PDF] (page 66)
to the superintendent. §C26-377.0 Presumptive Bearing Capacities of Soils.a. Satisfactory bearing materials shall be ledge rock in its natural bed, natural ...
§27-657 Foundations, General Requirements
on, or be carried down to, satisfactory bearing materials in such manner that the entire transmitted load will be distributed over the supporting soils at any ...
§27-664 Foundations, Test Pits
(a) of section 27-658 of article one of this subchapter, provided that such structures are supported by footings bearing on nominally satisfactory bearing ...
1804.2.2 Soils and Foundations, Controlled Fills
Fills shall be considered as satisfactory bearing material of the applicable class when placed in accordance with the following procedures ...