1016.0 Sand Interceptors
Go To Full Code Chapter
1016.1 Discharge
Where the discharge of a fixture or drain contains solids or semi-solids heavier than water that would be harmful to a drainage system or cause a stoppage within the system, the discharge shall be through a sand interceptor. Multiple floor drains shall be permitted to discharge into one sand interceptor.
1016.2 Authority Having Jurisdiction
Sand interceptors are required where the Authority Having Jurisdiction deems it advisable to have a sand interceptor to protect the drainage system.
1016.3 Construction and Size
Sand interceptors shall be built of brick or concrete, prefabricated coated steel, or other watertight material. The interceptor shall have an interior baffle for full separation of the interceptor into two sections. The outlet pipe shall be the same size as the inlet pipe of the sand interceptor, the minimum being 3 inches (80 mm), and the baffle shall have two openings of the same diameter as the outlet pipe and at the same invert as the outlet pipe. These openings shall be staggered so that there cannot be a straight line flow between the inlet pipe and the outlet pipe. The invert of the inlet pipe shall be no lower than the invert of the outlet pipe.
The sand interceptor shall have a minimum dimension of 2 square feet (0.2 m2) for the net free opening of the inlet section and a minimum depth under the invert of the outlet pipe of 2 feet (610 mm).
For each 5 gpm (0.3 L/s) flow or fraction thereof over 20 gpm (1.26 L/s), the area of the sand interceptor inlet section is to be increased by 1 square foot (0.09 m2). The outlet section shall at all times have a minimum area of 50 percent of the inlet section.
The outlet section shall be covered by a solid removable cover, set flush with the finished floor, and the inlet section shall have an open grating, set flush with the finished floor and suitable for the traffic in the area in which it is located.
1016.4 Separate Use
Sand and similar interceptors for every solid shall be so designed and located as to be readily accessible for cleaning, shall have a water seal of not less than 6 inches (152 mm), and shall be vented.
Upcodes Diagrams
Related Code Sections
1016.0 Traps and Interceptors, Sand Interceptors
a stoppage within the system, the discharge shall be through a sand interceptor. Multiple floor drains shall be permitted to discharge into one sand ...
1009.7 Traps and Interceptors, Discharge
The waste pipe from oil and sand interceptors shall discharge as approved by the Authority Having Jurisdiction ...
1009.1 Traps and Interceptors, Where Required
Interceptors (clarifiers) (including grease, oil, sand, solid interceptors, etc.) shall be required by the Authority Having Jurisdiction where ...
B 101.3 Explanatory Notes on Combination Waste and Vent Systems, Caution
Caution shall be exercised to exclude appurtenances delivering large quantities or surges of water (such as pumps, sand interceptors, etc.) from ...
1009.3 Traps and Interceptors, Design
Interceptors (clarifiers) for sand and similar heavy solids shall be so designed and located as to be readily accessible for cleaning and shall have ...