454.2.20.1 Sand Filters
Go To Full Code Chapter
454.2.20.1.1 Approved Types
Rapid sand filters [flow up to 5 gpm per square foot (0.3L/s)] shall be constructed in accordance with approved standards. Where high rate sand filters [flow in excess of 5 gpm per square foot (0.3 L/s)] are used, they shall be of an approved type. The circulation system and backwash piping shall be adequate for proper backwashing of said filter and shall provide backwash flow rates of at least 12 gpm per square foot (0.8 L/s) or rapid sand filters or 15 gpm per square foot (0.9 L/s) for high rate sand filters.
454.2.20.1.2 Instructions
Every filter system shall be provided with written operating instructions.
454.2.20.1.3 Filter System Equipment
On pressure-type filters, a means shall be provided to permit the release of internal pressure. A filter incorporating an automatic internal air release as its principal means of air release shall have lids which provide a slow and safe release of pressure as part of its design. A separation tank used in conjunction with a filter tank shall have as part of its design a manual means of air release or a lid which provides a slow and safe release of pressure as it is opened.
Upcodes Diagrams
Related Code Sections
454.2.20.1 Special Detailed Requirements Based on Use and Occupancy, Sand Filters
Rapid sand filters [flow up to 5 gpm per square foot (0.3L/s)] shall be constructed in accordance with approved standards. Where high rate sand ...
454.2.20.1 Special Detailed Requirements Based on Use and Occupancy, Sand Filters
Rapid sand filters [flow up to 5 gpm per square foot (0.3L/s)] shall be constructed in accordance with approved standards. Where high rate sand ...
454.2.20.1 Special Detailed Requirements Based on Occupancy and Use, Sand Filters
Rapid sand filters [flow up to 5 gpm per square foot (0.3L/s)] shall be constructed in accordance with approved standards. Where high rate sand ...
R4501.20.1 Private Swimming Pools, Sand Filters
Rapid sand filters (flow up to 5 gpm per square foot) shall be constructed in accordance with approved standards. Where high rate sand filters (flow ...
R4501.20.1 Private Swimming Pools, Sand Filters
R4501.20.1.1 Approved types. Rapid sand filters (flow up to 5 gpm per square foot) shall be constructed in accordance with approved standards. Where ...