1505.11 Same Trench as Potable Water Pipes
Go To Full Code Chapter
Reclaimed (recycled) water pipes shall be permitted to be run or laid in the same trench as potable water pipes with 12 inches (305 mm) minimum vertical and horizontal separation where both pipe materials are approved for use within a building. Where piping materials do not meet this requirement, the minimum horizontal separation shall be increased to 60 inches (1524 mm). The potable water piping shall be installed at an elevation above the reclaimed (recycled) water piping. Reclaimed (recycled) water pipes laid in the same trench or crossing building sewer or drainage piping shall be installed in accordance with this code for potable water piping.
Related Code Sections
1505.11 Alternate Water Sources for Nonpotable Applications, Same Trench as Potable Water Pipes
Reclaimed (recycled) water pipes shall be permitted to be run or laid in the same trench as potable water pipes with 12 inches (305 mm) minimum ...
1506.9.4 Alternate Water Sources for Nonpotable Applications, Near Underground Potable Water Pipe
On-site treated nonpotable water pipes shall be permitted to be run or laid in the same trench as potable water pipes with a 12 inch (305 mm) minimum ...
1502.4 Alternate Water Sources for Nonpotable Applications, Separation Requirements
Treated nonpotable water pipes shall be permitted to be run or laid in the same trench as potable water pipes with a 12 inch (305 mm) minimum vertical ...
1601.10 Nonpotable Rainwater Catchment Systems, Separation Requirements
pipes shall be permitted to be run or laid in the same trench as potable water pipes with a 12 inch (305 mm) minimum vertical and horizontal ...
P2910.13 Water Supply and Distribution, Separation Requirements for Nonpotable Water Piping
of Table P2906.5. The required separation distance shall not apply where a nonpotable water pipe is located in the same trench with a building sewer ...