B 103.0 Safety Shutoff Devices
Go To Full Code Chapter
B 103.1 General
Where a safety shutoff device is provided, it shall be checked for operation and adjustment in accordance with the appliance manufacturer's instructions. Where the device does not function properly to turn off the gas supply in the event of pilot outage or other improper operation, it shall be serviced or replaced with a new device. [NFPA 54:11.3]
Related Code Sections
B 103.0 Procedures to Be Followed to Place Gas Equipment in Operation, Safety Shutoff Devices
Where a safety shutoff device is provided, it shall be checked for operation and adjustment in accordance with the appliance manufacturer's ...
902.5 Installation of Specific Appliances, Safety Shutoff Devices for Unlisted LP-Gas Appliance Used Indoors
shutoff devices of the complete shutoff type. [NFPA 54:9.1.4] ...
507.8 Water Heaters, Safety Shutoff Devices for Unlisted LP-Gas Appliance Used Indoors
with safety shutoff devices of the complete shutoff type. [NFPA 54:9.1.4] ...
908.2.3 Installation of Specific Appliances, Multiple-Family or Public Use
Clothes dryers installed for multiple-family or public use shall be equipped with approved safety shutoff devices and shall be installed as specified ...