1006.6 Safety and Relief Valve Discharge
Go To Full Code Chapter
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. High-pressure-steam safety valves shall be vented to the outside of the structure. The discharge piping serving pressure relief valves, temperature relief valves and combinations of such valves shall:
- Not be directly connected to the drainage system.
- Discharge through an air break located in the same room as the appliance.
- Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air break.
- Serve a single relief device and shall not connect to piping serving any other relief device or equipment.
- Discharge to the floor, to the pan serving the boiler or storage tank, to a waste receptor or to the outdoors.
- Discharge in a manner that does not cause personal injury or structural damage.
- Discharge to a termination point that is readily observable by the building occupants.
- Not be trapped.
- Be installed so as to flow by gravity.
- Not terminate more than 6 inches (152 mm) above the floor or waste receptor.
- Not have a threaded connection at the end of such piping.
- Not have valves or tee fittings.
- Be constructed of those materials listed in Section 605.4 of the International Plumbing Code or materials tested, rated and approved for such use in accordance with ASME A112.4.1.
Upcodes Diagrams
Related Code Sections
1006.6 Boilers, Water Heaters and Pressure Vessels, Safety and Relief Valve Discharge
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall ...
1006.6 Boilers, Water Heaters and Pressure Vessels, Safety and Relief Valve Discharge
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. High-pressure-steam safety valves ...
1006.6 Boilers, Water Heaters and Pressure Vessels, Safety and Relief Valve Discharge
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. High-pressure-steam safety valves ...
Section 1006 Boilers, Water Heaters and Pressure Vessels, Safety and Pressure Relief Valves and Controls
discharge by gravity. Safety and relief valve ...
504.6.1.1 Water Heaters, Pumped Discharge of Relief Valve Collection
Pumps used to
discharge the clear water collection of relief valves shall have an operating
temperature equal to or exceeding that of the relief ...