// CODE SNIPPET
1910.261(b) Safe Practices
Go To Full Code Chapter
-
1910.261(b)(1) Lockouts
Devices such as padlocks shall be provided for locking out the source of power at the main disconnect switch. Before any maintenance, inspection, cleaning, adjusting, or servicing of equipment (electrical, mechanical, or other) that requires entrance into or close contact with the machinery or equipment, the main power disconnect switch or valve, or both, controlling its source of power or flow of material, shall be locked out or blocked off with padlock, blank flange, or similar device.
1910.261(b)(2) Emergency Lighting
Emergency lighting shall be provided wherever it is necessary for employees to remain at their machines or stations to shut down equipment in case of power failure. Emergency lighting shall be provided at stairways and passageways or aisleways used by employees for emergency exit in case of power failure. Emergency lighting shall be provided in all plant first aid and medical facilities.
Upcodes Diagrams
Related Code Sections
1910.420 Commercial Diving Operations, Safe Practices Manual
The employer shall develop and maintain a safe practices manual which shall be made available at the dive location to each dive team member ...
1910.184(c) Materials Handling and Storage, Safe Operating Practices
Whenever any sling is used, the following practices shall be observed ...
1910.269(e)(1) Special Industries, Safe Work Practices
The employer shall ensure the use of safe work practices for entry into, and work in, enclosed spaces and for rescue of employees from such spaces ...
1910.420(b)(2)(ii) Commercial Diving Operations,
Assignments and responsibilities of the dive team members ...