An automatic sprinkler system shall be installed at the top of rubbish and linen chutes and in their terminal rooms. Chutes shall have additional sprinkler heads installed at alternate floors and at the lowest intake. Where a rubbish chute extends through a building more than one floor below the lowest intake, the extension shall have sprinklers installed that are recessed from the drop area of the chute and protected from freezing in accordance with Section 903.3.1.1. Such sprinklers shall be installed at alternate floors, beginning with the second level below the last intake and ending with the floor above the discharge. Access to sprinklers in chutes shall be provided for servicing.

Related Code Sections

904.1.2 Alterations—Level 3, Rubbish and Linen Chutes
Rubbish and linen chutes located in the work area shall be provided with automatic sprinkler system protection or an approved automatic fire ...
904.1.2 Alterations—Level 3, Rubbish and Linen Chutes
Rubbish and linen chutes located in the work area shall be provided with automatic sprinkler system protection or an approved automatic fire ...