1810.3.3.1.7.2 Routine Soil Testing
Go To Full Code Chapter
Deep foundation elements shall develop ultimate load capacities of not less than 3 times the design working loads in the designated load-bearing layers when routine soil testing is used to determine soil properties. Analysis shall show that soil layers underlying the designated load-bearing layers do not cause the load-bearing safety factor to be less than 3.