803.6.2 Room Corner Test, Textiles
Go To Full Code Chapter
803.6.2.1 Method B Test Protocol
During the 40 kW exposure, the interior finish shall comply with Item 1. During the 150 kW exposure, the interior finish shall comply with Item 2. During the entire test, the interior finish shall comply with Item 3.
- During the 40 kW exposure, flames shall not spread to the ceiling.
-
During the 150 kW exposure, the interior finish shall comply with the following:
- Flame shall not spread to the outer extremities of the samples on the 8-foot by 12-foot (203 mm by 305 mm) walls.
- Flashover, as described in NFPA 265, shall not occur.
- The total smoke released throughout the NFPA 265 test shall not exceed 1000 m2.
Related Code Sections
803.6.2 Interior Finishes, Room Corner Test, Textiles
Textile wall coverings shall meet the criteria of Section 803.6.2.1 when tested in the manner intended for use in accordance with the Method B ...
803.5.1.1 Interior Finishes, Acceptance Criteria for NFPA 265
The total smoke release throughout the test shall not exceed 1,000 m2.
...
803.5.1 Interior Finish, Decorative Materials and Furnishings, Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.5.1.1 when tested in the manner intended for use ...
803.1.3 Interior Finishes, Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.1.3.1 when tested in the manner intended for use ...
803.5 Interior Finish, Decorative Materials and Furnishings, Textiles
The specimen shall not burn to the outer extremity of the 2-foot-wide (610 mm) samples mounted in the corner of the room. Burning droplets deemed ...