// CODE SNIPPET

803.1.3 Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings

Building Code 2015 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.1 General > 803.1.3 Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings
JUMP TO FULL CODE CHAPTER
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.1.3.1 when tested in the manner intended for use in accordance with the Method B protocol of NFPA 265 using the product-mounting system, including adhesive.

803.1.3.1 Acceptance Criteria for NFPA 265

The interior finish shall comply with the following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremities of the samples on the 8-foot by 12-foot (203 by 305 mm) walls.

3. Flashover, as defined in NFPA 265, shall not occur.

4. The total smoke released throughout the test shall not exceed 1,000 m2.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


803.5.1 Interior Finishes, Room corner test for textile wall coverings and expanded vinyl wall coverings
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.5.1.1 when tested in the manner intended for use ...
Building Code 2018 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.5 Textile wall coverings > 803.5.1 Room corner test for textile wall coverings and expanded vinyl wall coverings
803.1.3 Interior Finishes, Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings
Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.1.3.1 when tested in the manner intended for use ...
Building Code 2015 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.1 General > 803.1.3 Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings
803.7 Interior Finishes, Expanded vinyl wall coverings
Where used as interior wall finish materials, expanded vinyl wall coverings shall be tested in the manner intended for use, using the product ...
Building Code 2018 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.7 Expanded vinyl wall coverings
803.1.4 Interior Finishes, Acceptance Criteria for Textile and Expanded Vinyl Wall or Ceiling Coverings Tested to ASTM E84 or UL 723
Textile wall and ceiling coverings and expanded vinyl wall and ceiling coverings shall have a Class A flame spread index in accordance with ASTM E84 ...
Building Code 2015 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.1 General > 803.1.4 Acceptance Criteria for Textile and Expanded Vinyl Wall or Ceiling Coverings Tested to ASTM E84 or UL 723
803.8 Interior Finishes, Expanded Vinyl Ceiling Coverings
Where used as interior ceiling finish materials, expanded vinyl ceiling coverings shall be tested in the manner intended for use, using the product ...
Building Code 2015 of Utah > 8 Interior Finishes > 803 Wall and Ceiling Finishes > 803.8 Expanded Vinyl Ceiling Coverings
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US