803.1.2 Room Corner Test for Interior Wall or Ceiling Finish Materials
Go To Full Code Chapter
803.1.2.1 Acceptance Criteria for NFPA 286
The interior finish shall comply with the following:
- During the 40 kW exposure, flames shall not spread to the ceiling.
- The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
- Flashover, as defined in NFPA 286, shall not occur.
- The peak heat release rate throughout the test shall not exceed 800 kW.
- The total smoke released throughout the test shall not exceed 1,000 m2.
Upcodes Diagrams
Related Code Sections
803.1.2 Interior Finishes, Room Corner Test for Interior Wall or Ceiling Finish Materials
Interior wall or ceiling finish materials shall be permitted to be tested in accordance with NFPA 286. Interior wall or ceiling finish materials ...
803.1.2 Interior Finishes, Room Corner Test for Interior Wall or Ceiling Finish Materials
Interior wall or ceiling finish materials shall be permitted to be tested in accordance with NFPA 286. Interior wall or ceiling finish materials ...
803.5.1.1 Interior Finish, Decorative Materials and Furnishings, Acceptance Criteria for NFPA 265 Method B Test Protocol
Where testing to NFPA 265, the interior finish shall comply with the following: During the 40-kW exposure, flames shall not spread to the ceiling ...
Fire Code 2021 of Alabama > 8 Interior Finish, Decorative Materials and Furnishings > 803 Interior Wall and Ceiling Finish in Existing Buildings > 803.5 Textile Wall Coverings > 803.5.1 Room Corner Test for Textile Wall Coverings and Expanded Vinyl Wall Coverings > 803.5.1.1 Acceptance Criteria for NFPA 265 Method B Test Protocol
Section 803 Interior Finishes, Wall and Ceiling Finishes
for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria ...
Section 803 Interior Finish, Decorative Materials and Furnishings, Interior Wall and Ceiling Finish and Trim in Existing Buildings
to be tested in accordance with NFPA 286. Finishes tested in accordance with NFPA 286 shall comply with Section 803.1.2.1. Interior wall and ceiling ...