All roof tile adhesive used in adhesive set tile systems shall comply with the requirements set forth in TAS 110 and TAS 123. Physical properties shall be as follows:
1523.6.5.2.17.1
Tested for compressive strength in compliance with ASTM D1621 with a minimum strength of 18 psi (121 kPa) parallel to rise, and 12 psi (82.7 kPa) perpendicular to rise.
1523.6.5.2.17.2
Tested for density in compliance with ASTM D1622 with a minimum density of 1.6 lb/ft3 (25.6 kg/m3).
1523.6.5.2.17.3
Tested for tensile strength in compliance with ASTM D1623 with a minimum requirement of 28 psi (193 kPa) parallel to rise.
1523.6.5.2.17.4
Tested for dimensional stability taken from a free rise sample specimen. Tested in compliance with ASTM D2126 with a maximum volume change of +0.07-percent volume change at -40°F (-40°C) for two weeks; and +6.0-percent volume change at 158°F (70°C) and 100 percent RH for two weeks.
1523.6.5.2.17.5
Tested in compliance with ASTM D2856 from a free rise sample specimen with a minimum requirement for 85 percent.
1523.6.5.2.17.6
Tested for water absorption in compliance with ASTM D2842 with a maximum requirement of 10 percent.
1523.6.5.2.17.7
Tested in compliance with ASTM E96 for moisture vapor transmission for a maximum of 3.1 perms.