// CODE SNIPPET
2223.9 Roof Purlins and Wall Girts
Go To Full Code Chapter
2223.9.1
Adequate bracing shall be provided to the compression flanges of secondary members with special attention to those members subject to uplift or outward pressures where no roof or wall sheets are attached to provide such bracing. Sag rods shall not be considered bracing when located in the neutral axis of the web of the secondary members.
2223.9.2
2223.9.3
The ends and bearing points of secondary members shall be designed to carry 100 percent of dead, live and collateral loads superimposed on them by wind.
2223.9.4
Upward or outward forces of wind are to be calculated without live and collateral loads. When downward or inward forces caused by wind are involved, the dead forces plus collateral load forces must be combined but the roof live load may be omitted.
Upcodes Diagrams
Related Code Sections
2223.9 Steel, Roof Purlins and Wall Girts
purlins and wall girts shall be laterally braced in addition to relying on deck and panel diaphragm action ...
2223.9 Steel, Roof Purlins and Wall Girts
purlins and wall girts shall be laterally braced in addition to relying on deck and panel diaphragm action ...
2223.9 Steel, Roof Purlins and Wall Girts
purlins and wall girts shall be laterally braced in addition to relying on deck and panel diaphragm action ...
2223.9.1 Steel,
or outward pressures where no roof or wall sheets are attached to provide such bracing. Sag rods shall not be considered bracing when located in the neutral ...
2223.9.4 Steel,
, the dead forces plus collateral load forces must be combined but the roof live load may be omitted ...