A4.203.1.2.1 Roof Deck Insulation, or Ducts in Conditioned Space
Go To Full Code Chapter
Meet one of the three options for the location of ducts and air handlers as well as insulation R-values and installation of a radiant barrier as specified in Title 24, Part 6, Section 150.1(c)9A or B:
- Below roof deck insulation with a minimum R-value of 19; or,
- Continuous above deck insulation with a minimum R-8 and with an air space present between the roofing and the roof deck; or,
- All ducts and air handlers in conditioned space as specified in the Title 24, Part 6, Reference Appendix RA3.1.
Upcodes Diagrams
Related Code Sections
A4.203.1.2.1 Residential Voluntary Measures, Roof Deck Insulation, or Ducts in Conditioned Space
insulation with a minimum R-8 and with an air space present between the roofing and the roof deck; or,
All ducts and air handlers in conditioned space ...
A4.203.1.2.1 Residential Voluntary Measures, Roof Deck Insulation, or Ducts in Conditioned Space
with a minimum R-8 and with an air space present between the roofing and the roof deck; or, All ducts and air handlers in conditioned space ...
A4.203.1 Residential Voluntary Measures, Energy Efficiency
above deck insulation with a minimum R-8 and with an air space present between the roofing and the roof deck; or, All ducts and air handlers ...
A5.205.3.4.3 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Ducts
If insulation is installed on an existing space-conditioning duct, it shall comply with Section 605 of the California Mechanical Code (CMC) ...
A5.205.3.4.3 Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Ducts
If insulation is installed on an existing space-conditioning duct, it shall comply with Section 605 of the California Mechanical Code (CMC) ...