408.3.1 Roof Coverings—Solar Reflectance and Thermal Emittance
Go To Full Code Chapter
Where roof coverings are used for compliance with Section 408.3, roof coverings shall comply with Section 408.3.1.1 or 408.3.1.2. The values for solar reflectance and thermal emittance shall be determined by an independent laboratory accredited by a nationally recognized accreditation program. Roof products shall be listed and labeled and certified by the manufacturer demonstrating compliance.
TABLE 408.3.1
REFLECTANCE AND EMITTANCE
REFLECTANCE AND EMITTANCE
ROOF SLOPE | MINIMUM AGED SOLAR REFLECTANCE | MINIMUM AGED THERMAL EMITTANCE | MINIMUM AGED SRI |
2:12 or less | 0.55 | 0.75 | 60 |
Greater than 2:12 | 0.30 | 0.75 | 25 |
408.3.1.1 Roof Products Testing
Roof products shall be tested for a minimum three-year aged solar reflectance in accordance with ASTM E 1918, ASTM C 1549 or the CRRC-1 Standard and thermal emittance in accordance with ASTM C 1371, ASTM E 408 or the CRRC-1 Standard, and shall comply with the minimum values in Table 408.3.1.
408.3.1.2 Solar Reflectance Index
Roof products shall be permitted to use a solar reflectance index (SRI) where the calculated value is in compliance with Table 408.3.1 values for minimum aged SRI. The SRI value shall be determined using ASTM E 1980 with a convection coefficient of 2.1 Btu/h-ft2 (12 W/m2 × k) based on three-year aged roof samples tested in accordance with the test methods in Section 408.3.1.1.
Related Code Sections
408.3.1 Site Development and Land Use, Roof Coverings—Solar Reflectance and Thermal Emittance
for solar reflectance and thermal emittance shall be determined by an independent laboratory accredited by a nationally recognized accreditation program. Roof ...
C402.3 [CE] Commercial Energy Efficiency, Roof Solar Reflectance and Thermal Emittance
REFLECTANCE AND EMITTANCE OPTIONSa
Three-year aged solar reflectanceb of 0.55 and 3-year aged thermal emittancec of 0.75
Three-year-aged solar ...
C402.3 [CE] Commercial Energy Efficiency, Roof Solar Reflectance and Thermal Emittance
TABLE C402.3
MINIMUM ROOF REFLECTANCE AND EMITTANCE OPTIONSa
Three-year-aged solar reflectanceb of 0.55 and 3-year aged thermal emittancec ...
C402.3.1 [CE] Commercial Energy Efficiency, Aged Roof Solar Reflectance
Where an aged solar reflectance required by Section C402.3 is not available, it shall be determined in accordance with Equation 4-3. (Equation 4-3 ...
3.3.158.2 Definitions, Reflective Insulation
Thermal insulation consisting of one or more low-emittance surfaces bounding one or more enclosed air spaces. (SAF-INT) ...