Section 322 Road Tunnels, Bridges and Other Limited Access Highways
Go To Full Code Chapter
322.1 Scope
This section shall govern the design, installation, operation and maintenance of road tunnels, bridges and other limited access highways used or designed to be used by motor vehicles.
322.2 Design and Installation
The design and installation of fire safety and life safety systems for road tunnels, bridges and other limited access highways, including emergency ventilation systems, emergency voice communication systems, fire protection systems and means of egress, shall be in accordance with NFPA 502, as modified by FC Appendix B; the Electrical Code; the provisions of the construction codes applicable to fire safety and life safety systems; and this section.
322.2.1 Fire Scenario Design Parameters
Approved fire scenarios used for designing road tunnels shall be in accordance with NFPA 502, as modified by FC Appendix B, and the following:
- The worst case scenario, as set forth in NFPA 502, as modified by FC Appendix B, shall be used for designs.
- Computational fluid dynamics analysis for the fire simulation shall be performed for an approved period of time, both with and without mitigating systems, including but not limited to ventilation and sprinkler protection.
- The tenable condition parameters reported in the computational fluid dynamics analysis, including but not limited to heat, visibility and carbon monoxide, shall be precisely reported in the analysis.
322.3 Operation and Maintenance
The operation and maintenance of road tunnels, bridges and other limited access highways used or designed to be used by motor vehicles shall be in accordance with NFPA 502, as modified by FC Appendix B.
322.4 Construction Site Fire Safety
Construction operations of road tunnels, bridges and other limited access highways shall be conducted in accordance with Chapter 33 of the Building Code; this code, including FC Chapter 33; and NFPA 502, as modified by FC Appendix B. Approved fire extinguishing systems shall be provided for construction shanties and construction storage facilities and areas.
Upcodes Diagrams
Related Code Sections
1103.2.10 Accessibility, Non-Grade Single-Occupant Structures
that are accessed only by bridges or underground tunnels, are not required to be accessible ...
1103.2.10 Accessibility, Nongrade Single-Occupant Structures
that are accessed only by bridges or underground tunnels, are not required to be accessible ...
3304.3.5 Safeguards During Construction or Demolition, Notification and Approval of the New York City Transit Authority, the Metropolitan Transportation Authority, and the Port Authority of New York and New Jersey
but not limited to rail and subway lines, stations, station entrance and access points, bridges, tunnels, bus depots, access roads, fan plants, pump rooms ...
1103.2.9 Accessibility, Equipment Spaces
or equipment catwalks, water or sewerage treatment pump rooms and stations, electrical substations and transformer vaults, and highway and tunnel ...
§27-373 Means of Egress, Horizontal Exits
; of a balcony or exterior vestibule leading around the end of a fire division to another fire area or building; or it may be a bridge or tunnel between two ...