454.1.9.5 River Rides
Go To Full Code Chapter
454.1.9.5.1
River rides shall be constructed within the limits of sound engineering practice.
454.1.9.5.2
River rides shall be constructed on concrete or other impervious materials with a nontoxic, smooth and slip-resistant finish. These rides shall be of such shape and design as to be operated in a safe and sanitary manner.
454.1.9.5.3
The recirculation-filtration system of the river ride shall be capable of a minimum of one turnover every 3 hours.
454.1.9.5.4
The maximum water depth of the river ride shall not exceed 3 feet (914 mm) unless justified to the jurisdictional building department's satisfaction by the design engineer.
454.1.9.5.5
Decking shall be provided at the entrance and exit points as necessary to provide safe patron access but shall not be smaller than 10 feet (3048 mm) in width and length. Additional decking along the ride course is not required except that decking shall be required at lifeguard locations and emergency exit points.
454.1.9.5.6
Access and exit shall be provided at the start and end of the ride and additional exit locations shall be located along the ride course as necessary to provide for the safety of the patrons.
Propulsion jets shall be installed in the walls of the river ride. In the alternative, propulsion jets may be installed in the floor if they are covered by a grate that will inhibit entrapment or injury of the pool patrons' feet or limbs.
Upcodes Diagrams
Related Code Sections
454.1.9.5 Special Detailed Requirements Based on Use and Occupancy, River Rides
River rides shall be constructed within the limits of sound engineering practice ...
454.1.9.5 Special Detailed Requirements Based on Use and Occupancy, River Rides
River rides shall be constructed within the limits of sound engineering practice ...
454.1.9.5 Special Detailed Requirements Based on Occupancy and Use, River Rides
River rides shall be constructed within the limits of sound engineering practice ...
454.1.9.5.1 Special Detailed Requirements Based on Occupancy and Use,
River rides shall be constructed within the limits of sound engineering practice ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.5 River Rides > 454.1.9.5.1
454.1.9.5.3 Special Detailed Requirements Based on Use and Occupancy,
The recirculation-filtration system of the river ride shall be capable of a minimum of one turnover every 3 hours ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 454 Swimming Pools and Bathing Places (Public and Private) > 454.1 Public Swimming Pools and Bathing Places > 454.1.9 Water Recreation Attractions and Specialized Pools > 454.1.9.5 River Rides > 454.1.9.5.3