// CODE SNIPPET
603.7 Rigid Duct Penetrations
Go To Full Code Chapter
Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required by Section 607. Ducts in a private garage that penetrate a wall or ceiling that separates a dwelling from a private garage shall be continuous, shall be constructed of sheet steel having a thickness of not less than 0.0187 inch (0.4712 mm) (No. 26 gage) and shall not have openings into the garage. Fire and smoke dampers are not required in such ducts passing through the wall or ceiling separating a dwelling from a private garage except where required by Chapter 7 of the International Building Code.
Upcodes Diagrams
Related Code Sections
603.7 Duct Systems, Rigid Duct Penetrations
Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required ...
603.7 Duct Systems, Rigid Duct Penetrations
Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required ...
603.7 Duct Systems, Rigid Duct Penetrations
Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required ...
6.7.5 Systems and Equipment, Duct Penetrations
Ducts that penetrate construction intended to protect against x-ray, magnetic, radio frequency interference (RFI), or other radiation shall ...
614.2 Specific Appliances, Duct Penetrations
Ducts that exhaust clothes dryers shall not penetrate or be located within any fireblocking, draftstopping or any wall, floor/ceiling or other ...