5106.2 Retail Aerosol Product Displays Not Exceeding 8 Feet High
Go To Full Code Chapter
5106.2.1 Maximum Quantity
Only aerosol products being used for display purposes shall be stored for sale in retail display areas and the total quantity of such aerosol products shall not exceed the amounts set forth in FC Table 5106.2.1.
For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m2.
MAXIMUM NET WEIGHT PER FLOOR (pounds)b
|
|||
FLOOR
|
Unprotecteda
|
Protected in accordance with FC5106.2a, c
|
Protected in accordance with FC5106.3c
|
Basement, cellar or other area below grade |
Not allowed
|
500
|
500
|
Ground |
2,500
|
10,000
|
10,000
|
Upper |
500
|
2,000
|
Not allowed
|
- The total quantity shall not exceed 1,000 pounds net weight in any one 100-square-foot retail display area.
- Per 25,000-square-foot retail display area.
- Minimum Ordinary Hazard Group 2 wet-pipe sprinkler system throughout the retail sales occupancy.
5106.2.2 Display of Containers
Aerosol containers shall not be stacked more than 6 feet (1829 mm) high from the base of the aerosol array to the top of the aerosol array unless the containers are placed on fixed shelving or otherwise secured in an approved manner. When storage or retail display is on shelves, the height of such storage or retail display to the top of aerosol containers shall not exceed 8 feet (2438 mm) from the floor.
Exception: Storage or display protected in accordance with FC5106.3.
5106.2.3 Combustible Cartons
Aerosol products located in retail display areas shall be removed from combustible cartons.
Exceptions:
- Display areas that use a portion of combustible cartons, which consist of only the bottom panel and not more than 2 inches (51 mm) of side panel are allowed.
- When the display area is protected in accordance with Tables 6.3.2.7(a) through 6.3.2.7(l) of NFPA 30B, storage of aerosol products in combustible cartons is allowed.
5106.2.4 Retail Display Sprinkler System
When a sprinkler system is required for the
protected retail display of aerosol products, the wet-pipe sprinkler system shall be in accordance with this code, and the construction codes, including the Building Code. The
minimum system design shall be for an Ordinary Hazard Group 2 occupancy. The system shall
be provided throughout the retail display area.
Upcodes Diagrams
Related Code Sections
414.1.2.1 Special Detailed Requirements Based on Use and Occupancy, Aerosols
Level 2 and 3 aerosol products shall be stored and displayed in accordance with the New York City Fire Code ...
414.1.2.1 Special Detailed Requirements Based on Use and Occupancy, Aerosols
Level 2 and 3 aerosol products shall be stored and displayed in accordance with the New York City Fire Code ...
414.1.2.1 Special Detailed Requirements Based on Use and Occupancy, Aerosols
Level 2 and 3 aerosol products shall be stored and displayed in accordance with the New York City Fire Code See the New York City Fire Code ...
307.1 Use and Occupancy Classification, High-Hazard Group H
personal or household products in their original packaging used in retail display or commonly used building materials.
Buildings and structures ...
307.1.1 Use and Occupancy Classification, Uses Other Than Group H
York City Mechanical Code.
Corrosive personal or household products in their original packaging used in retail display.
Commonly used corrosive ...