Uplift resistance of common foundations are given in Table R403.1.2. Uplift resistance of these foundations may be increased by increasing the size of the concrete footing. When determining the modified uplift resistance the added weight shall be reduced by multiplying by a factor of 0.6. Other foundation systems shall be engineered in accordance with the Florida Building Code, Building.
FOUNDATION UPLIFT (ASD) DESIGN DETAILS
FOOTING TYPE T
(inches)
W
(inches)
SLAB/WALL1 RESISTANCE
(plf)
NOTES
A Mono 20 12 6 502 3
Mono 20 16 6 585 3
B Mono Interior 20 12 13 796 3
Mono Interior 20 16 13 879 3
C 12" Stem/Joist 10 20 228 436 1, 2, 3
D Mono 20 12 6 502
Mono 20 16 6 585
E Mono Interior 20 12 13 796
Mono Interior 20 16 13 879
F Stem/Joist 10 20 208 2, 3
G Stem/Slab 10 20 6 460 3
H Stem/Slab 10 12 6 377 3
Stem/Slab 10 20 6 460 3
For SI: 1 inch = 25.4 mm.
  1. Tributary width of 31/2" slab or weight of stemwall and bond beam.
  2. First floor dead load multiplied by 0.6 may also be included.
  3. All footing dowel bars shall be same size as wall steel, shall have a standard 90-degree hook, and shall be embedded a minimum of 6 inches. Dowel bars shall lap vertical wall reinforcement a minimum of 25 inches.
Upcodes Diagrams

Related Code Sections

R403.1.2 Foundations, Resistance to Uplift
Uplift resistance of common foundations are given in Table R403.1.2. Uplift resistance of these foundations may be increased by increasing the size ...
R403.1.2 Foundations, Resistance to Uplift
Uplift resistance of common foundations are given in Table R403.1.2. Uplift resistance of these foundations may be increased by increasing the size ...
R403.1.2 Foundations, Resistance to Uplift
Uplift resistance of common foundations are given in Table R403.1.2. Uplift resistance of these foundations may be increased by increasing the size ...