Residential swimming pools shall comply with Sections 3109.4.1 through 3109.4.3.
Exception: A swimming pool with a power safety cover or a spa with a safety cover complying with ASTM F 1346.
3109.4.1 Barrier Height and Clearances
The top of the barrier shall be at least 48 inches (1219 mm) above grade measured on the side of the barrier that faces away from the swimming pool. The maximum vertical clearance between grade and the bottom of the barrier shall be 2 inches (51 mm) measured on the side of the barrier that faces away from the swimming pool. Where the top of the pool structure is above grade, the barrier is authorized to be at ground level or mounted on top of the pool structure, and the maximum vertical clearance between the top of the pool structure and the bottom of the barrier shall be 4 inches (102 mm).
3109.4.1.1 Openings
Openings in the barrier shall not allow passage of a 4-inch-diameter (102 mm) sphere.
3109.4.1.2 Solid Barrier Surfaces
Solid barriers which do not have openings shall not contain indentations or protrusions except for normal construction tolerances and tooled masonry joints.
3109.4.1.3 Closely Spaced Horizontal Members
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches (1143 mm), the horizontal members shall be located on the swimming pool side of the fence. Spacing between vertical members shall not exceed 13/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 13/4 inches (44 mm) in width.
3109.4.1.4 Widely Spaced Horizontal Members
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is 45 inches (1143 mm) or more, spacing between vertical members shall not exceed 4 inches (102 mm). Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 13/4 inches (44 mm) in width.
3109.4.1.5 Chain Link Dimensions
Maximum mesh size for chain link fences shall be a 21/4 inch square (57 mm square) unless the fence is provided with slats fastened at the top or the bottom which reduce the openings to no more than 13/4 inches (44 mm).
3109.4.1.6 Diagonal Members
Where the barrier is composed of diagonal members, the maximum opening formed by the diagonal members shall be no more than 13/4 inches (44 mm).
3109.4.1.7 Gates
Access doors or gates shall comply with the requirements of Sections 3109.4.1.1 through 3109.4.1.6 and shall be equipped to accommodate a locking device. Pedestrian access doors or gates shall open outward away from the pool and shall be self-closing and have a self-latching device. Doors or gates other than pedestrian access doors or gates shall have a self-latching device. Release mechanisms shall be in accordance with Sections 1008.1.9 and 1109.12. Where the release mechanism of the self-latching device is located less than 54 inches (1372 mm) above the finished surface, the release mechanism shall be located on the pool side of the door or gate at least 3 inches (76 mm) below the top of the door or gate, and the door or gate and barrier shall have no opening greater than 1/2 inch (12.7 mm) within 18 inches (457 mm) of the release mechanism.
3109.4.1.8 Dwelling Wall as a Barrier
Where a wall of a dwelling serves as part of the barrier, one of the following shall apply:
  1. Doors with direct access to the pool through that wall shall be equipped with an alarm that produces an audible warning when the door and/or its screen, if present, are opened. The alarm shall be listed and labeled in accordance with UL 2017. In dwellings not required to be Accessible units, Type A units or Type B units, the deactivation switch shall be located 54 inches (1372 mm) or more above the threshold of the door. In dwellings required to be Accessible units, Type A units or Type B units, the deactivation switch(es) shall be located at 54 inches (1372 mm) maximum and 48 inches (1219 mm) minimum above the threshold of the door.
  2. The pool shall be equipped with a power safety cover that complies with ASTM F 1346.
  3. Other means of protection, such as self-closing doors with self-latching devices, which are approved, shall be accepted so long as the degree of protection is not less than the protection required by Section 3109.4.1.8, Item 1 or 2.
3109.4.1.9 Pool Structure as Barrier
Where an above-ground pool structure is used as a barrier or where the barrier is mounted on top of the pool structure, and the means of access is a ladder or steps, then the ladder or steps either shall be capable of being secured, locked or removed to prevent access, or the ladder or steps shall be surrounded by a barrier which meets the requirements of Sections 3109.4.1.1 through 3109.4.1.8. When the ladder or steps are secured, locked or removed, any opening created shall not allow the passage of a 4-inch-diameter (102 mm) sphere.
3109.4.2 Indoor Swimming Pools
Walls surrounding indoor swimming pools shall not be required to comply with Section 3109.4.1.8.
3109.4.3 Prohibited Locations
Barriers shall be located so as to prohibit permanent structures, equipment or similar objects from being used to climb the barriers.
Upcodes Diagrams

Related Code Sections

3109.4 Special Construction, Residential Swimming Pool Enclosures
Residential swimming pools shall comply with Sections 3109.4.1 through 3109.4.3. Exception: A swimming pool with a power safety cover or a spa ...
3109.4 Special Construction, Residential Swimming Pool Enclosures
Residential swimming pools shall be completely enclosed by a barrier complying with Sections 3109.4.1 through 3109.4.3. Exception: A swimming ...