A fire alarm system shall be installed in accordance with Section 907.2.24.in residential hospices. When automatic sprinkler systems or automatic fire detectors are installed, such systems or detectors shall be connected to the building fire alarm system.
907.2.24.1 Initiation
Initiation of the fire alarm system shall be by manual and automatic means. Approved automatic fire detectors shall be provided in boiler and furnace rooms, kitchens, laboratories, shops, gift shops, commissaries, laundry and soiled linen rooms, mechanical and electrical rooms, locker rooms, storage rooms, janitors' closets, trash collection rooms, lounges, and similar areas. Automatic smoke detectors shall be provided in sleeping rooms, corridors, and spaces open to the corridors.
Exception: Manual fire alarm boxes are not required at exits if manual fire alarm boxes are located at all nurses' stations or other continuously attended staff locations, provided such fire alarm boxes are visible and continuously accessible and that travel distances required by Section 907.4.1.are not exceeded.
907.2.24.2 Notification
Activation of the fire alarm system or automatic sprinkler system shall initiate a general evacuation signal. In addition, the fire alarm system shall be monitored by an approved central station service in accordance with Section 903.4.1.
Exception: In lieu of audible notification appliances, visible notification appliances shall be allowed to be used in sleeping areas.
Upcodes Diagrams

Related Code Sections

907.2.24 Fire Protection Systems, Residential Hospices
A fire alarm system shall be installed in accordance with Section 907.2.24.in residential hospices. When automatic sprinkler systems or automatic ...
907.2.24 Fire Protection Systems, Residential Hospices
A fire alarm system shall be installed in accordance with Section 907.2.24 in residential hospices. When automatic sprinkler systems or automatic ...
903.2.8.3 Fire Protection Systems, Residential Hospice Facilities
containing a residential hospice facility. Exception: An automatic sprinkler system installed in accordance with Section 903.3.1.2.or 903.3.1.3.shall ...