[F] 413.4 Residential Fueling Appliance Installation
JUMP TO FULL CODE CHAPTER
Residential fueling appliances shall be installed in accordance with Sections 413.4.1 through 413.4.3.
Residential fueling appliances shall be listed in accordance with ANSI NGV 5.1. Residential fueling appliances shall be installed in accordance with the appliance manufacturer's installation instructions.
Residential fueling appliances shall not be rigidly connected to the gas supply piping.
A residential fueling appliance installed indoors or used for indoor fueling shall comply with all of the following:
- The capacity shall not exceed 5 cubic feet per minute (0.14 m3/min) of natural gas.
- Fuel gas from the pressure relief and blowdown systems shall be vented to the outdoors.
- A methane gas detector shall be installed in the room or space containing the appliance or where fueling occurs and shall be located not lower than 6 inches (152 mm) from the highest point in the room or space. The detector shall be set to activate at onefifth of the lower limit of flammability of natural gas and shall be interlocked with the residential fuel appliance to stop or prevent its operation upon activation. The detector shall have an audible or visible alarm.
- The capacity of a residential fueling appliance installed outdoors for outdoor fueling shall not exceed 10 feet cubic per minute (0.28 m3/min) of natural gas. Residential fueling appliances located outdoors shall be installed on a firm, noncombustible base.
Related Code Sections
413.4 Gas Piping Installations, Residential Fueling Appliance Installation
Residential fueling appliances shall be installed in accordance with Sections 413.4.1 through 413.4.3 ...
Fuel Gas Code 2018 of Kansas > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.4 Residential Fueling Appliance Installation
413.3 Gas Piping Installations, Location of Dispensing Operations and Equipment
not located in vaults complying with the International Fire Code and other than residential fueling appliances shall not be installed: Beneath power lines ...
Fuel Gas Code 2018 of Kansas > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.3 Location of Dispensing Operations and Equipment
805.2 Chimneys and Vents, Solid Fuel Appliances
Factory-built chimneys installed in dwelling units with solid fuel-burning appliances shall comply with the Type HT requirements of UL 103 ...
Mechanical Code 2018 of Kansas > 8 Chimneys and Vents > 805 Factory-Built Chimneys > 805.2 Solid Fuel Appliances
R1005.3 Chimneys and Fireplaces, Solid-Fuel Appliances
Factory-built chimneys installed in dwelling units with solid-fuel-burning appliances shall comply with the Type HT requirements of UL 103 ...
Residential Code 2018 of Kansas > 10 Chimneys and Fireplaces > R1005 Factory-Built Chimneys > R1005.3 Solid-Fuel Appliances
Section 101 Scope and Administration, General
herein. The installation of fuel gas distribution piping and equipment , fuel gas-fired appliances and fuel gas-fired appliance venting systems shall ...