• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects General Contractor Building Official & Plans Examiner Inspectors Owner Subcontractors Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

612.0 Residential Fire Sprinkler Systems

California Plumbing Code 2016 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems
JUMP TO FULL CODE CHAPTER

612.1 Where Required

Where residential sprinkler systems are required in one and two family dwellings or townhouses, the systems shall be installed by an ASSE Series 7000 certified installer in accordance with this section or NFPA 13D. This section shall be considered equivalent to NFPA 13D. Partial residential sprinkler systems shall be permitted to be installed in buildings not required to be equipped with a residential sprinkler system.

612.2 Types of Systems

This section shall apply to standalone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire sprinkler system shall provide potable water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system shall be separate and independent from the potable water distribution system.

612.3 Sprinklers

Sprinklers shall be installed in accordance with Section 612.3.1 through Section 612.3.7.

612.3.1 Required Sprinkler Locations

Sprinklers shall be installed to protect all floor areas of a dwelling unit in one and two family dwellings or townhouses.

Exceptions:
  1. Attics, crawl spaces, and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In attics, crawl spaces, and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be provided to protect the equipment; however, sprinklers shall not be required in the remainder of the space.
  2. Clothes closets, linen closets, and pantries that do not exceed 24 square feet (2.2 m2) in area, with the smallest dimension not exceeding 3 feet (914 mm) and having wall and ceiling surfaces of gypsum board.
  3. Bathrooms and toilet rooms that do not exceed 55 square feet (5.1 m2) in area.
  4. Detached garages; carports; with no habitable space above; open attached porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.
  5. Covered unheated projections of the building at entrances/exits provided it is not the only means of egress from the dwelling unit.
  6. Ceiling pockets that meet the following requirements:

    1. The total volume of an unprotected ceiling pocket does not exceed 100 cubic feet (2.83 m3).
    2. The entire floor under the unprotected ceiling pocket is protected by the sprinklers at the lower ceiling elevation.
    3. Each unprotected ceiling pocket is separated from an adjacent unprotected ceiling pocket by not less than a 10 feet (3048 mm) horizontal distance.
    4. The interior finish of the unprotected ceiling pocket is noncombustible material.
    5. Skylights not exceeding 32 square feet (2.97 m2).

612.3.2 Sprinkler Installation

Sprinklers shall be listed residential sprinklers and shall be installed in accordance with the sprinkler manufacturer's installation instructions.

612.3.3 Temperature Rating and Separation From Heat Sources

Sprinklers shall have a temperature rating of not less than 135°F (57°C) and not more than 170°F (77°C). Sprinklers shall be separated from heat sources in accordance with the sprinkler manufacturer's installation instructions.

Exception: Sprinklers located close to a heat source in accordance with Section 612.3.3.1 shall be intermediate temperature sprinklers.

612.3.3.1 Intermediate Temperature Sprinklers

Sprinklers shall have an intermediate temperature rating of not less than 175°F (79°C) and not more than 225°F (107°C) where installed in the following locations:
  1. Directly under skylights, where the sprinkler is exposed to direct sunlight.
  2. In attics and concealed spaces located directly beneath a roof.
  3. Within the distance to a heat source in accordance with Table 612.3.3.1.

TABLE 612.3.3.1
LOCATIONS WHERE INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIRED
HEAT SOURCE DISTANCE FROM HEAT
SOURCE1
MINIMUM DISTANCE2
(inches)
MAXIMUM
DISTANCE
(inches)
Fireplace, Side of Open or Recessed
Fireplace
12 36
Fireplace, Front of Recessed Fireplace 36 60
Coal and Wood burning Stove 12 42
Kitchen Range Top 9 18
Oven 9 18
Vent Connector or Chimney Connector 9 18
Heating Duct, Not Insulated 9 18
Hot Water Pipe, Not Insulated 6 12
Side of Ceiling or Wall Warm Air
Register
12 24
Front of Wall Mounted Warm Air
Register
18 36
Water Heater, Furnace, or Boiler 3 6
Luminaire up to 250 Watts 3 6
Luminaire 250 Watts up to 499 Watts 6 12
For SI units: 1 inch = 25.4 mm

Notes:
1   Distances shall be measured in a straight line from the nearest edge of the heat source to the nearest edge of the sprinkler.
2   Sprinklers shall not be located at distances less than the minimum table distance unless the sprinkler listing allows a lesser distance.

612.3.4 Freezing Areas

The piping system shall be protected in accordance with the requirements of Chapter 3. Where sprinklers are required in areas that are subject to freezing, dry-sidewall or dry-pendent sprinklers extending from a non-freezing area into a freezing area shall be installed. Where fire sprinkler piping cannot be adequately protected against freezing, the system shall be designed and installed in accordance with NFPA 13D.

612.3.5 Coverage Area Limit

The area of coverage of a single sprinkler shall be based on the sprinkler listing and the sprinkler manufacturer's installation instructions. The area of coverage of a single sprinkler shall not exceed 400 square feet (37.16 m2).

612.3.6 Obstructions to Sprinkler Coverage

The water discharge from a sprinkler shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional sprinklers shall not be required where sprinkler separation from obstructions is in accordance with the requirements of Table 612.3.6, or the minimum distances specified in the sprinkler manufacturer's installation instructions.

TABLE 612.3.6
MINIMUM SEPARATION FROM OBSTRUCTION
PENDENT SPRINKLERS
DISTANCE FROM DEFLECTOR TO PLANE AT BOTTOM OF OBSTRUCTION (A)
(inches)
MINIMUM DISTANCE TO OBSTRUCTION (B)
(feet)
1 11/2
3 3
5 4
7 41/2
9 6
11 61/2
14 7


SIDEWALL SPRINKLER
SIDE OBSTRUCTION
DISTANCE FROM DEFLECTOR TO PLANE AT BOTTOM OF OBSTRUCTION (A)
(inches)
MINIMUM DISTANCE TO OBSTRUCTION (B)
(feet)
1 11/2
3 3
5 4
7 41/2
9 6
11 61/2
14 7


SIDEWALL SPRINKLER
SIDE OBSTRUCTION
DISTANCE FROM DEFLECTOR TO PLANE AT BOTTOM OF OBSTRUCTION (A)
(inches)
MINIMUM DISTANCE TO OBSTRUCTION (B)
(feet)
1 8
2 10
3 11
4 12
6 13
7 14
9 15
11 16
14 17
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

612.3.6.1 Additional Requirements for Pendent Sprinklers

Pendent sprinklers located within 3 feet (914 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire, or similar object shall be considered to be obstructed and additional sprinklers shall be provided.

612.3.6.2 Additional Requirements for Sidewall Sprinklers

Sidewall sprinklers located within 5 feet (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire, or similar object shall be considered to be obstructed and additional sprinklers shall be provided.

612.3.7 Sprinkler Modifications Prohibited

Sprinklers shall not be painted, caulked, or modified. A sprinkler that has been painted, caulked, modified, or damaged shall be replaced with a new sprinkler.

612.3.8 Backflow Protection

A backflow preventer shall not be required to separate a sprinkler system from the water distribution system, provided that:
  1. The system complies with NFPA 13D or Section R313, and
  2. Piping material are suitable for potable water in accordance with the California Plumbing Code, and
  3. The system does not contain antifreeze or have a fire department connection.

612.4 Sprinkler Piping System

Sprinkler piping systems shall be installed in accordance with Section 612.4.1 through Section 612.4.5.

612.4.1 General

Sprinkler piping shall be installed in accordance with the requirements for water distribution piping. Sprinkler piping shall comply with the material requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold water distribution piping system.

612.4.2 Nonmetallic Pipe and Tubing

Nonmetallic pipe and tubing, such as CPVC, PEX-AL-PEX, PE-RT, and PEX, shall be certified for residential sprinkler installations and shall have a pressure rating of not less than 130 psi (896 kPa) at 120°F (49°C).

612.4.2.1 Nonmetallic Pipe Protection

Nonmetallic pipe and tubing systems shall be protected from exposure to the occupied space by a layer of not less than 3/8 of an inch (9.5 mm) thick gypsum wallboard, 1/2 of an inch (12.7 mm) thick plywood, or other material having a 15 minute fire rating.

Exceptions:
  1. Pipe protection shall not be required in areas that are not required to be protected with sprinklers in accordance with Section 612.3.1.
  2. Pipe protection shall not be required where exposed piping is permitted by the pipe third party listing.

612.4.2.2 Sprinkler Installation on Systems Assembled With Solvent Cement

The solvent cementing of fittings shall be completed and threaded adapters for sprinklers shall be verified as being clear of excess cement prior to the installation of sprinklers on systems assembled with solvent cement.

612.4.3 Shutoff Valves Prohibited

Shutoff valves shall not be installed in a location where the valve would isolate piping serving one or more sprinklers. Shutoff valves shall only be permitted for the entire water distribution system.

612.4.4 Single Dwelling Limit

The sprinkler piping beyond the service valve located at the beginning of the water distribution system shall serve only one dwelling unit.

612.4.5 Drain

A 1/2 inch (15 mm) drain for the sprinkler system shall be provided on the system side of the water distribution shutoff valve.

612.5 Sprinkler Piping Design

Sprinkler piping systems shall be sized in accordance with Section 612.5.1 through Section 612.5.3.2.2.

612.5.1 Determining System Design Flow

The sizing of the sprinkler piping system shall be based on the flow rate and pressure of each sprinkler in accordance with Section 612.5.1.1 and the number of sprinklers in accordance with Section 612.5.1.3.

612.5.1.1 Determining Required Flow Rate for Each Sprinkler

The minimum flow rate and pressure for each residential sprinkler shall be in accordance with the manufacturer's published data for the specific sprinkler model based on the following:
  1. The area of coverage
  2. The ceiling configuration
  3. The temperature rating
  4. Additional conditions specified by the sprinkler manufacturer

612.5.1.2 System Flow Rate

The flow rate used for sizing the sprinkler piping system shall be based on the following:
  1. The flow rate for a room having only one sprinkler shall be the flow rate required for the sprinkler in accordance with Section 612.5.1.1.
  2. The flow rate for a room having two or more sprinklers shall be determined by identifying the sprinkler in the room with the highest required flow rate in accordance with Section 612.5.1.1, and multiplying that flow rate by 2.
  3. Where the sprinkler manufacturer specifies different criteria for ceiling configurations that are not smooth, flat, and horizontal the required flow rate for that room shall be in accordance with the sprinkler manufacturer's instructions.
  4. The flow rate used for sizing the sprinkler system shall be the flow required by the room with the largest flow rate in accordance with Section 612.5.1.2(1), Section 612.5.1.2(2), and Section 612.5.1.2(3).
  5. For the purpose of this section, it shall be permissible to reduce the flow rate for a room by subdividing the space into two or more rooms, where each room is evaluated separately with respect to the required design flow rate. Each room shall be bounded by walls and a ceiling. Openings in walls shall have a lintel not less than 8 inches (203 mm) in depth and each lintel shall form a solid barrier between the ceiling and the top of the opening.

612.5.1.3 Fire Sprinklers Attached Garages, and Carports With Habitable Space Above

Attached garages and carports with habitable space above shall be protected by fire sprinklers in accordance with this Section and Section R313. Protection shall be provided in accordance with one of the following:
  1. Residential Sprinklers installed in accordance with their listing.
  2. Extended Coverage sprinklers discharging water not less than their listed flow rate for Light Hazard in accordance with NFPA 13.
  3. Quick-Response spray sprinklers at light hazard spacing in accordance with NFPA 13 designed to discharge at 0.05 gpm/ft2 density (minimum).
The system demand shall be permitted to be limited to the number of sprinklers in the compartment but shall not exceed two sprinklers for hydraulic calculation purposes. Garage doors shall not be considered obstructions and shall be permitted to be ignored for placement and calculation of sprinklers.

612.5.2 Sprinkler Pipe Water Supply

The water supply for a multipurpose or stand alone sprinkler system shall be provided by the public water main, private water main, private well system, or storage tank. The water supply required shall be determined in accordance with Section 612.5.1.2 at a pressure not less than that used in accordance with Section 612.5.3. Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler system demand at the point where the systems are connected, to determine the size of common piping and the size of the total water supply requirements where no provision is made to prevent flow into the domestic water system upon operation of a sprinkler.

612.5.2.1 Water Pressure From Individual Sources

Where a dwelling unit water supply is from a tank system, a private well system, a pump or a combination of these, the available water pressure shall be based on the minimum pressure control setting of the pump.
SEE MORE

Related Code Sections


612.0 Water Supply and Distribution, Residential Fire Sprinkler Systems
Where residential sprinkler systems are required in one and two-family dwellings or townhouses, the systems shall be installed by personnel ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems
612.0 Water Supply and Distribution, Residential Fire Sprinkler Systems
Where residential sprinkler systems are required in one and two family dwellings or townhouses, the systems shall be installed by an ASSE Series 7000 ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems
612.2 Water Supply and Distribution, Types of Systems
This section shall apply to stand-alone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems > 612.2 Types of Systems
612.5 Water Supply and Distribution, Sprinkler Piping Design
Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler system demand at the point where ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems > 612.5 Sprinkler Piping Design
612.5 Water Supply and Distribution, Sprinkler Piping Design
domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler system demand at the point where the systems are connected ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 612.0 Residential Fire Sprinkler Systems > 612.5 Sprinkler Piping Design
Help Contact Us Privacy Terms
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE