Each patient shall have access to a toilet room without having to enter the general corridor area or the resident bed area in a shared resident room. One toilet room shall serve no more than two patients and no more than two resident rooms. The door to the toilet room shall be side hinged and either swing out from the toilet room, or be equipped with emergency release hardware. Sliding doors equipped with sliding door hardware located on the resident room side of the wall and not equipped with a bottom door track shall be permitted. If a sliding door is used in a resident toilet or bath room, a D-shaped handle at least 4 inches (10.16 cm) long shall be provided to open the door. The sliding door shall permit access, and negate the need to push against a patient who may have collapsed within the toilet room. Unless otherwise required by this code, this door shall be at least 36 inches (914.4 mm) wide. A lavatory shall be provided in each resident toilet room.