Where reshoring of flat-slab construction is required, the formwork cannot be stripped until the concrete has acquired sufficient strength to safely support its weight and the load thereon, or temporary preshores are provided supporting the slab at intervals of no more than 8 feet (2438 mm) on center to be replaced by reshores prior to placing concrete on the floor above. Reshores must be installed and remain in place until the concrete reaches full or sufficient strength to sustain the superimposed loads to which the concrete will be subjected.
Upcodes Diagrams

Related Code Sections

1906.6.5 Concrete, Reshoring Flat Slabs
Where reshoring of flat slab construction is required, the formwork cannot be stripped until the concrete has acquired sufficient strength to safely ...