Section 120.1 Requirements for Ventilation
Nonresidential, high-rise residential and hotel/motel buildings shall comply with the requirements of Sections 120.1(a) through 120.1(e).
(a) General requirements.
All enclosed spaces in a building shall be ventilated in accordance with the requirements of this section and the California Building Code.
Exception to Section 120.1(a)1: Refrigerated warehouses and other spaces or buildings that are not normally used for human occupancy and work.
- The outdoor air-ventilation rate and air-distribution assumptions made in the design of the ventilating system shall be clearly identified on the plans required by Section 10-103 of Title 24, Part 1.
(b) Design requirements for minimum quantities of outdoor air. Every space in a building shall be designed to have outdoor air ventilation according to Item 1 or 2 below:
Natural ventilation.
Naturally ventilated spaces shall be permanently open to and within 20 feet of operable wall or roof openings to the outdoors, the openable area of which is not less than 5 percent of the conditioned floor area of the naturally ventilated space. Where openings are covered with louvers or otherwise obstructed, openable area shall be based on the free unobstructed area through the opening.
Exception to Section 120.1(b)1A: Naturally ventilated spaces in high-rise residential dwelling units and hotel/motel guest rooms shall be open to and within 25 feet of operable wall or roof openings to the outdoors.
- The means to open required operable openings shall be readily accessible to building occupants whenever the space is occupied.
Mechanical ventilation. Each space that is not naturally ventilated under Item 1 above shall be ventilated with a mechanical system capable of providing an outdoor air rate no less than the larger of:
- The conditioned floor area of the space times the applicable ventilation rate from Table 120.1-A; or
15 cfm per person times the expected number of occupants. For meeting the requirement in Section 120.1(b)2B for spaces without fixed seating, the expected number of occupants shall be either the expected number specified by the building designer or one half of the maximum occupant load assumed for egress purposes in the California Building Code, whichever is greater. For spaces with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code.
Exception to Section 120.1(b)2: Transfer air. The rate of outdoor air required by Section 120.1(b)2 may be provided with air transferred from other ventilated spaces if:
- None of the spaces from which air is transferred have any unusual sources of indoor air contaminants; and
- The outdoor air that is supplied to all spaces combined is sufficient to meet the requirements of Section 120.1(b)2 for each space individually.
(c) Operation and control requirements for minimum quantities of outdoor air.
Times of occupancy. The minimum rate of outdoor air required by Section 120.1(b)2 shall be supplied to each space at all times when the space is usually occupied.
Exception 1 to Section 120.1(c)1: Demand control ventilation. In intermittently occupied spaces that do not have processes or operations that generate dusts, fumes, mists, vapors or gasses and are not provided with local exhaust ventilation (such as indoor operation of internal combustion engines or areas designated for unvented food service preparation), the rate of outdoor air may be reduced if the ventilation system serving the space is controlled by a demand control ventilation device complying with Section 120.1(c)4 or by an occupant sensor ventilation control device complying with Section 120.1(c)5.
Exception 2 to Section 120.1(c)1: Temporary reduction. The rate of outdoor air provided to a space may be reduced below the level required by Section 120.1(b)2 for up to 30 minutes at a time if the average rate for each hour is equal to or greater than the required ventilation rate.
- Pre-occupancy. The lesser of the minimum rate of outdoor air required by Section 120.1(b)2 or three complete air changes shall be supplied to the entire building during the one-hour period immediately before the building is normally occupied.
Required demand control ventilation. HVAC systems with the following characteristics shall have demand ventilation controls complying with Section 120.1(c)4:
- They have an air economizer; and
- They serve a space with a design occupant density, or a maximum occupant load factor for egress purposes in the California Building Code, greater than or equal to 25 people per 1,000 square feet (40 square feet or less per person); and
They are either:
- Single zone systems with any controls; or
Multiple zone systems with Direct Digital Controls (DDC) to the zone level.
Exception 1 to Section 120.1(c)3: Classrooms, call centers, office spaces served by multiple zone systems that are continuously occupied during normal business hours with occupant density greater than 25 people per 1,000 square feet as specified by Section 120.1(b)2B, healthcare facilities and medical buildings, and public areas of social services buildings are not required to have demand control ventilation.
Exception 2 to Section 120.1(c)3: Where space exhaust is greater than the design ventilation rate specified in Section 120.1(b)2B minus 0.2 cfm per square foot of conditioned area.
Exception 3 to Section 120.1(c)3: Spaces that have processes or operations that generate dusts, fumes, mists, vapors or gases and are not provided with local exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, or beauty salons shall not install demand control ventilation.
Exception 4 to Section 120.1(c)3: Spaces with an area of less than 150 square feet, or a design occupancy of less than 10 people as specified by Section 120.1(b)2B.
Exception 5 to Section 120.1(c)3: Spaces with an area of less than 1,500 square feet complying with Section 120.1(c)5.
Demand control ventilation devices.
- For each system with demand control ventilation, CO2 sensors shall be installed in each room that meets the criteria of Section 120.1(c)3 with no less than one sensor per 10,000 square feet of floor space. When a zone or a space is served by more than one sensor, a signal from any sensor indicating that CO2 is near or at the setpoint within a space shall trigger an increase in ventilation to the space;
- CO2 sensors shall be located in the room between 3 feet and 6 feet above the floor or at the anticipated height of the occupants heads;
Demand ventilation controls shall maintain CO2 concentrations less than or equal to 600 ppm plus the outdoor air CO2 concentration in all rooms with CO2 sensors;
Exception to Section 120.1(c)4C: The outdoor air ventilation rate is not required to be larger than the design outdoor air ventilation rate required by Section 120.1(b)2 regardless of CO2 concentration.
Outdoor air CO2 concentration shall be determined by one of the following:
- CO2 concentration shall be assumed to be 400 ppm without any direct measurement; or
- CO2 concentration shall be dynamically measured using a CO2 sensor located within 4 feet of the outdoor air intake.
- When the system is operating during hours of expected occupancy, the controls shall maintain system outdoor air ventilation rates no less than the rate listed in Table 120.1-A times the conditioned floor area for spaces with CO2 sensors, plus the rate required by Section 120.1(b)2 for other spaces served by the system, or the exhaust air rate, whichever is greater.
- CO2 sensors shall be certified by the manufacturer to be accurate within plus or minus 75 ppm at a 600 and 1000 ppm concentration when measured at sea level and 25°C, factory calibrated and certified by the manufacturer to require calibration no more frequently than once every 5 years. Upon detection of sensor failure, the system shall provide a signal which resets to supply the minimum quantity of outside air to levels required by Section 120.1(b)(2) to the zone serviced by the sensor at all times that the zone is occupied.
- The CO2 sensor(s) reading for each zone shall be displayed continuously, and shall be recorded on systems with DDC to the zone level.
Occupant sensor ventilation control devices. When occupancy sensor ventilation devices are required by Section 120.2(e)3 or when meeting Exception 5 to Section 120.1(c)3, occupant sensors shall be used to reduce the rate of outdoor air flow when occupants are not present in accordance with the following:
- Occupant sensors shall meet the requirements in Section 110.9(b)4 and shall have suitable coverage and placement to detect occupants in the entire space ventilated. Occupant sensors controlling lighting may be used for ventilation as long as the ventilation signal is independent of daylighting, manual lighting overrides or manual control of lighting. When a single zone damper or a single zone system serves multiple rooms, there shall be an occupancy sensor in each room and the zone is not considered vacant until all rooms in the zone are vacant.
- One hour prior to normal scheduled occupancy, the occupancy sensor ventilation control shall allow pre-occupancy purge as described in Section 120.1(c)2.
- Within 30 minutes after being vacant for all rooms served by a zone damper on a multiple zone system, and the space temperature is between the heating and cooling setpoints, then no outside air is required and supply air shall be zero.
- Within 30 minutes after being vacant for all rooms served by a single zone system, the single zone system shall cycle off the supply fan when the space temperature is between the heating and cooling setpoints.
In spaces equipped with an occupant sensor, when vacant during hours of expected occupancy and the occupied ventilation rate required by Section 120.1(b)2 is not provided, then the system or zone controls shall cycle or operate to maintain the average outdoor air rate over an averaging period of 120 minutes equal to 25 percent of the rate listed in Table 120.1-A.
Exception to Section 120.1(c)5: If demand control ventilation is implemented as required by Section 120.1(4).
(d) Ducting for zonal heating and cooling units. Where a return plenum is used to distribute outdoor air to a zonal heating or cooling unit, which then supplies the air to a space in order to meet the requirements of Section 120.1(b)2, the outdoor air shall be ducted to discharge either:
- Within 5 feet of the unit; or
- Within 15 feet of the unit, substantially toward the unit, and at a velocity not less than 500 feet per minute.
(e) Design and control requirements for quantities of outdoor air.
- All mechanical ventilation and space-conditioning systems shall be designed with and have installed ductwork, dampers and controls to allow outside air rates to be operated at the larger of (1) the minimum levels specified in Section 120.1(b)1; or (2) the rate required for make-up of exhaust systems that are required for an exempt or covered process, for control of odors, or for the removal of contaminants within the space.
- All variable air volume mechanical ventilation and space-conditioning systems shall include dynamic controls that maintain measured outside air ventilation rates within 10 percent of the required outside air ventilation rate at both full and reduced supply airflow conditions. Fixed minimum damper position is not considered to be dynamic and is not an allowed control strategy.
- Measured outdoor air rates of constant volume mechanical ventilation and space-conditioning systems shall be within 10 percent of the required outside air rate.
MINIMUM VENTILATION RATES
TYPE OF USE | CFM PER SQUARE FOOT OF CONDITIONED FLOOR AREA |
Auto repair workshops | 1.50 |
Barber shops | 0.40 |
Bars, cocktail lounges and casinos | 0.2 |
Beauty shops | 0.40 |
Coin-operated dry cleaning | 0.30 |
Commercial dry cleaning | 0.45 |
High-rise residential | Ventilation rates specified by the California Building Code |
Hotel guest rooms (less than 500 ft2) | 30 cfm/guest room |
Hotel guest rooms (500 ft2 or greater) | 0.15 |
Retail stores | 0.20 |
All others | 0.15 |