// CODE SNIPPET
1104.0 Requirements for Refrigerant and Refrigeration System Use
JUMP TO FULL CODE CHAPTER
Refrigeration systems shall be limited in application in accordance with Table 1104.1, and the requirements of Section 1104.0.
TABLE 1104.1 PERMISSIBLE REFRIGERATION SYSTEMS1
OCCUPANCY GROUP3 | HIGH-PROBABILITY SYSTEM | LOW PROBABILITY SYSTEM | MACHINERY ROOM |
---|---|---|---|
A-1 | Group A1 only | Any | Any |
A-2 | Group A1 only | Any | Any |
A-3 | Group A1 only | Any | Any |
A-4 | Group A1 only | Any | Any |
B | Group A12 only | Any | Any |
E | Group A1 only | Any | Any |
F-1 | Group A12 only | Any | Any |
F-2 | Any2 | Any | Any |
H-1 | Any | Any | Any |
H-2 | Any | Any | Any |
H-3 | Any | Any | Any |
H-4 | Group A1 only | Any | Any |
H-5 | Group A1 only | Any | Any |
I-1 | None | Any | Any |
I-2 | Group A1 only | Any | Any |
I-3 | None | Any | Any |
I-4 | Group A1 only | Any | Any |
M | Group A12 only | Any | Any |
R-1 | Group A1 only | Any | Any |
R-2 | Group A1 only | Any | Any |
R-3 | Group A1 only | Any | Any |
R-4 | Group A1 only | Any | Any |
S-1 | Group A12 only | Any | Any |
S-2 | Any2 | Any | Any |
U | Any | Any | Any |
Notes:
1 See Section 1104.0.
2 A refrigerant shall be permitted to be used within a high-probability system where the room or space is in accordance with Section 1104.4.
3 Occupancy classifications are defined in the building code.
The concentration of refrigerant in a complete discharge of an independent circuit of high-probability systems shall not exceed the amounts shown in Table 1102.3, except as provided in Section 1104.3 and Section 1104.4. The volume of occupied space shall be determined in accordance with Section 1104.2.1 through Section 1104.2.3.
Exceptions:
- Listed equipment containing not more than 6.6 pounds (2.99 kg) of refrigerant, regardless of the refrigerant safety classification, provided the equipment is installed in accordance with the listing and with the manufacturer's installation instructions.
- Listed equipment for use in laboratories with more than 100 square feet (9.29 m2) of space per person, regardless of the refrigerant safety classification, provided that the equipment is installed in accordance with the listing and the manufacturer's installation instructions. [ASHRAE 15:7.2]
The volume used to convert from refrigerant concentration limits to refrigerating system quantity limits for refrigerants in Section 1104.2 shall be based on the volume of space to which refrigerant disperses in the event of a refrigerant leak. [ASHRAE 15:7.3]
Where a refrigerating system or part thereof is located in one or more enclosed occupied spaces that do not connect through permanent openings or HVAC ducts, the volume of the smallest occupied space shall be used to determine the refrigerant quantity limit in the system. Where different stories and floor levels connect through an open atrium or mezzanine arrangement, the volume to be used in calculating the refrigerant quantity limit shall be determined by multiplying the floor area of the lowest space by 8.2 feet (2499 mm). [ASHRAE 15:7.3.1]
Where a refrigerating system or a part thereof is located within an air handler, in an air distribution duct system, or in an occupied space served by a mechanical ventilation system, the entire air distribution system shall be analyzed to determine the worst-case distribution of leaked refrigerant. The worst case or the smallest volume in which the leaked refrigerant disperses shall be used to determine the refrigerant quantity limit, subject to the criteria in accordance with Section 1104.2.3.1 through Section 1104.2.3.3. [ASHRAE 15:7.3.2]
Closures in the air distribution system shall be considered. Where one or more spaces of several arranged in parallel are capable of being closed off from the source of the refrigerant leak, their volume(s) shall not be used in the calculation.
Exceptions: The following closure devices shall not be considered:
- Smoke dampers, fire dampers, and combination smoke and fire dampers that close only in an emergency not associated with a refrigerant leak.
- Dampers, such as variable-air-volume (VAV) boxes, that provide limited closure where airflow is not reduced below 10 percent of its maximum with the fan running. [ASHRAE 15:7.3.2.1]
The space above a suspended ceiling shall not be included in calculating the refrigerant quantity limit in the system unless such space is part of the air supply or return system. [ASHRAE 15:7.3.2.2]
The RCL value required in Section 1104.2 shall be reduced by 50 percent for the areas of institutional occupancies. The total of Group A2, B2, A3, and B3 refrigerants shall not exceed 550 pounds (249.5 kg) in the occupied areas and machinery rooms of institutional occupancies.
Exception: The total of all Group A2L refrigerants shall not be limited in machinery rooms of institutional occupancies.
Section 1104.2 shall not apply in industrial occupancies and refrigerated rooms where in accordance with the following:
- The space(s) containing the machinery is (are) separated from other occupancies by tight construction with tight-fitting doors.
- Access is restricted to authorized personnel.
- The floor area per occupant is not less than 100 square feet (9.29 m2).
Exception: The minimum floor area shall not apply where the space is provided with egress directly to the outdoors or into approved building exits.
- Refrigerant detectors are installed with the sensing location and alarm level as required in refrigeration machinery rooms in accordance with Section 1106.2.2.2.
- Open flames and surfaces exceeding 800°F (427°C) shall not be permitted where a Group A2, B2, A3, or B3 refrigerant, is used.
- Electrical equipment that is in accordance with Class 1, Division 2, of NFPA 70 where the quantity of a Group A2, B2, A3, or B3 refrigerant in an independent circuit is capable of exceeding 25 percent of the lower flammability limit (LFL) upon release to the space based on the volume determined in accordance with Section 1104.2.1 through Section 1104.2.3.
- Refrigerant containing parts in systems exceeding 100 horsepower (74.6 kW) compressor drive power, except evaporators used for refrigeration or dehumidification, condensers used for heating, control and pressure-relief valves for either, and connecting piping, are located in a machinery room or outdoors. [ASHRAE 15:7.2.2]
The total of Group A2, B2, A3, and B3 refrigerants, other than Group A2L and B2L refrigerants shall not exceed 1100 pounds (498.9 kg) without approval by the Authority Having Jurisdiction. Institutional Occupancies shall comply with Section 1104.3.
In nonindustrial occupancies, Group A2, A3, B1, B2, and B3 refrigerants shall not be used in high-probability systems for human comfort.
Recovered refrigerants shall not be reused except in the system from which they were removed or as provided in Section 1104.7.2 or Section 1104.7.3. Where contamination is evident by discoloration, odor, acid test results, or system history, recovered refrigerants shall be reclaimed in accordance with Section 1104.7.3. [ASHRAE 15:7.5.1.4]
Recycled refrigerants shall not be reused except in systems using the same refrigerant and lubricant designation and belonging to the same owner as the systems from which they were removed. Where contamination is evident by discoloration, odor, acid test results, or system history, recycled refrigerants shall be reclaimed in accordance with Section 1104.7.3.
Exception: Drying shall not be required in order to use recycled refrigerants where water is the refrigerant, is used as an absorbent or is a deliberate additive. [ASHRAE 15:7.5.1.5]
Used refrigerants shall not be reused in a different owner's equipment unless tested and found to be in accordance with the requirements of AHRI 700. Contaminated refrigerants shall not be used unless reclaimed and is in accordance with AHRI 700. [ASHRAE 15:7.5.1.6]
Refrigerants, including refrigerant blends, with different designations as in accordance with Table 1102.3 shall not be mixed in a system.
Exception: Addition of a second refrigerant shall be permitted where specified by the equipment manufacturer to improve oil return at low temperatures. The refrigerant and amount added shall be in accordance with the manufacturer's instructions. [ASHRAE 15:7.5.1.7]
A change in the type of refrigerant in a system shall not be made without notifying the Authority Having Jurisdiction, the user, and due observance of safety requirements. The refrigerant being considered shall be evaluated for suitability. [ASHRAE 15:5.3]
Related Code Sections
1104.0 Refrigeration, Requirements for Refrigerant and Refrigeration System Use
Refrigeration systems shall be limited in application in accordance with Table 1104.1, and the requirements of Section 1104.0. TABLE 1104.1 ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use
1104.3 Refrigeration, Institutional Occupancies
The RCL value required in Section 1104.2 shall be reduced by 50 percent for the areas of institutional occupancies. The total of Group A2, B2, A3 ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.3 Institutional Occupancies
1104.4 Refrigeration, Industrial Occupancies and Refrigerated Rooms
containing parts in systems exceeding 100 horsepower (74.6 kW) compressor drive power, except evaporators used for refrigeration or dehumidification ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.4 Industrial Occupancies and Refrigerated Rooms
1104.6 Refrigeration, Applications for Human Comfort and for Nonindustrial Occupancies
In nonindustrial occupancies, Group A2, A3, B1, B2, and B3 refrigerants shall not be used in high-probability systems for human comfort ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.6 Applications for Human Comfort and for Nonindustrial Occupancies
1104.7.2 Refrigeration, Recycled Refrigerants
Recycled refrigerants shall not be reused except in systems using the same refrigerant and lubricant designation and belonging to the same owner ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.7 Refrigerant Type and Purity > 1104.7.2 Recycled Refrigerants