1926.704 Requirements for Precast Concrete
Go To Full Code Chapter
1926.704(a)
Precast concrete wall units, structural framing, and tilt-up wall panels shall be adequately supported to prevent overturning and to prevent collapse until permanent connections are completed.
1926.704(b)
Lifting inserts which are embedded or otherwise attached to tilt-up precast concrete members shall be capable of supporting at least two times the maximum intended load applied or transmitted to them.
1926.704(c)
Lifting inserts which are embedded or otherwise attached to precast concrete members, other than the tilt-up members, shall be capable of supporting at least four times the maximum intended load applied or transmitted to them.
1926.704(d)
Lifting hardware shall be capable of supporting at least five times the maximum intended load applied or transmitted to the lifting hardware.
1926.704(e)
No employee shall be permitted under precast concrete members being lifted or tilted into position except those employees required for the erection of those members.
[FR 41088, Oct. 5, 1989]
[FR 41088, Oct. 5, 1989]
Related Code Sections
1926.704 Concrete and Masonry Construction, Requirements for Precast Concrete
precast concrete members being lifted or tilted into position except those employees required for the erection of those members. [FR 41088, Oct. 5 ...
1926.501(b)(12) Fall Protection, "Precast Concrete Erection"
Each employee engaged in the erection of precast concrete members (including, but not limited to the erection of wall panels, columns, beams ...
1926.700(b)(5) Concrete and Masonry Construction,
"Precast concrete" means concrete members (such as walls, panels, slabs, columns, and beams) which have been formed, cast, and cured prior to final ...
1926.700 Concrete and Masonry Construction, Scope, Application, and Definitions Applicable to This Subpart
This subpart sets forth requirements to protect all construction employees from the hazards associated with concrete and masonry construction ...
1926.1201(a) Confined Spaces in Construction,
; water mains; precast concrete and other pre-formed manhole units; drilled shafts; enclosed beams; vessels; digesters; lift stations; cesspools; silos; air ...