UpCodes logo
Go To Full Code Chapter
Alterations of portions or components of buildings shall comply with Sections 1003.2.1 through 1003.2.7.
Exceptions:
  1. The total cost of improvements required by Sections 1003.2.1 through 1003.2.7 shall not be required to exceed 10 percent of the costs of the alterations exclusive of land and building site improvements.
  2. This section shall not require compliance that exceeds that required for systems regulated by Chapters 6 through 8 of this code.
  3. Materials, assemblies and components regulated by Sections 1003.2.1 through 1003.2.7 that are dependent upon properties of other concealed materials, assemblies or system components to function properly and where the properties of the concealed materials, assemblies or components are unknown or insufficient and will not be revealed during construction.
  4. Alterations are not required to comply with the requirements of Sections 1003.2.1 through 1003.2.7 where the code official determines the alterations to be infeasible based upon the existing configuration of spaces, unless those spaces or portions thereof will be reconfigured as part of the alteration project.
  5. Where a tenant in a multi-tenant building does not have control within that tenant space of a complete system or item, compliance for that complete system or item shall not be required.
  6. Where the total cost of the alteration to the existing building is less than the percent of the value of the building as indicated in Table 1003.2, compliance with Section 1003.2 shall not be required. The percent value of the building shall be determined by the original construction cost plus completed improvement costs of the building.
TABLE 1003.2
MINIMUM VALUES FOR ADDITIONAL
REQUIREMENTS TO ALTERATIONS
BUILDING SIZE (square feet)PERCENT OF BUILDING VALUE
Less than 5,00020
5,000 — 50,00010
50,001 — 500,0001
over 500,0000
For SI: 1 square foot = 0.0929 m2.
1003.2.1 Metering Devices
Dedicated individual utility or private metering devices that measure and verify energy and water use within the building or space shall be provided for at least one of the following:
  1. Electrical energy consumption for individual tenant spaces.
  2. Water consumption for individual tenant spaces.
  3. Natural gas or fuel oil consumption for individual tenant spaces.
  4. Lighting loads.
  5. Motor and drive loads.
  6. Chiller part-load efficiency.
  7. Cooling loads.
  8. Economizer and heat recovery loads.
  9. Boiler efficiencies.
  10. Building process systems and equipment loads.
  11. Water consumption for landscape irrigation.
1003.2.2 Heating, Ventilating and Air-Conditioning
Heating, ventilating and air-conditioning systems and equipment shall be in accordance with the following:
  1. Time clock and automatic time switch controls that can turn systems off and on according to building occupancy requirements shall be provided and connected to the following HVAC equipment: chillers and other space-cooling equipment, chilled water pumps, boilers and other space-heating devices, hot water pumps, heat exchanger circulation pumps, supply fans, return fans, and exhaust fans. Where occupant override is provided, it shall be designed with a timer to automatically revert to time clock and automatic time switch controls in not longer than 12 hours.
    Exception: A time clock or automatic time switch controls shall not be required for spaces where any of the following conditions exist:
    1. A time clock is not required by Section C403.2.4.3 of the International Energy Conservation Code.
    2. There is 24-hour occupancy materials with special atmospheric requirements dependent on 24-hour space conditioning.
    3. A majority of the areas of the building served by the system are under setback thermostat control.
    4. Manufacturer's specifications stipulate that the system must not be shut off.
  2. Functional outside air economizers shall be provided on all cooling systems of more than 41/2 tons total cooling capability, 54,000 Btu/h, or more than 1800 cfm (9.144 m3/s @ m2) air flow, provided manufacturer's guidelines are available for adding the economizer to the existing system.
    Exception: An outside air economizer shall not be required for buildings or special uses where 100 percent outside air for ventilation is required or where any of the following conditions exist:
    1. Section C403.3.1 of the International Energy Conservation Code would not require an economizer.
    2. The existing system has a water-based economizer.
    3. The existing system does not have an outside air intake.
    4. Special economizer operations such as, but not limited to, carefully controlled humidity would require more energy use than is conserved.
    5. There is insufficient space to install necessary equipment.
    6. Installation of an economizer would require major modifications to the building's life safety system.
    7. The existing system is a multi-zone system where the same intake air is used at the same time for either heating or cooling in different parts of the building.
  3. HVAC piping and ducts, including those located above suspended ceilings, shall comply with Sections 606.3 and 606.4.
    Exception: Additional insulation shall not be required for piping where any of the following conditions exist:
    1. Additional insulation shall not be required for piping where any of the following conditions exist:
      1. It is located within HVAC equipment;
      2. It is located within conditioned space that conveys fluids between 60°F (15.6°C) and 105°F (40.6°C);
      3. Piping that is already insulated and the insulation is in good condition; or
    2. Where HVAC ducts and piping are installed in a building cavity or interstitial framing space of insufficient width to accommodate the duct or pipe and the insulation required by Section 606.3 and Table 606.4, the insulation thickness shall be permitted to have the maximum thickness that the wall can accommodate, but shall not be less than 1/2-inch (12.7 mm) thick.
  4. Where central heat is intended to be replaced with individual electric space heaters, the application for the electrical permit shall include documentation demonstrating that the new electric heaters will not consume more energy than the existing nonelectric heaters.
  5. Boiler systems shall have been cleaned and tuned within one year prior to the alteration. Boilers shall be equipped with an outdoor air lock-out thermostat or a temperature reset control.
  6. Chillers shall be equipped with an outdoor air lockout thermostat and chilled water reset control.
  7. A maximum 5-year phase out plan shall be provided for buildings with existing systems that use CFC-based refrigerants.
  8. 8. Where mechanical and electrical systems and equipment are joined with microprocessors that communicate with each other or to a computer, a properly integrated building automation system shall be installed to optimize energy, operations, and indoor comfort. The building automation system shall:
    1. Allow the owner to set up schedules of operation for the equipment and provide equipment optimal start with adaptive learning;
    2. Provide trim and respond capabilities based on zone demand;
    3. Offer the ability to monitor energy usage, including the ability to meter electric, gas, water, steam, hot water, chilled water, and fuel oil services;
    4. Offer economizing based on enthalpy calculation and/or CO2 set point control;
    5. Offer load shedding when power companies are at peak demand and need; and
    6. Offer the ability to send alarms to alert building owner, manager, or operator when problems occur due to system failures.
1003.2.3 Service Water Systems
Service water systems and equipment shall be in accordance with the following:
  1. Water heater and hot water storage tanks shall have a combined minimum total of external and internal insulation value of R-16.
  2. Accessible hot and cold water supply and distribution pipes shall comply with Section 607.6. The insulation shall not be required to extend beyond the building thermal envelope.
  3. Circulating pump systems for hot water supply purposes other than comfort heating shall be controlled as specified in Section 607.7.
  4. Showerhead, toilet, urinal and faucet flow rates shall be in accordance with this code.
1003.2.4 Lighting
Lighting systems and equipment shall be in accordance with sections C405.2.2.3 and C405.2.4 of the International Energy Conservation Code.
1003.2.5 Swimming Pools and Spas
Swimming pools and spas and their equipment shall be in accordance with the following:
  1. Heated swimming pools and spas shall be equipped with a cover listed and labeled in accordance with ASTM F 1346, or a liquid pool cover feed system, for unoccupied hours.
    Exception: A cover shall not be required for indoor pools or spas in which water temperature is less than 80°F (26.7°C) during time of nonuse.
  2. Backwash systems shall be based on pressure drop and shall not be based on a timer.
  3. Pool and spa recirculation pumps shall be under timeclock control.
    Exception: Filtration pumps where the public health standard requires 24-hour pump operation.
  4. Heaters shall have been cleaned and tuned for efficiency within one year prior to the alteration. Where this has not been done, the heaters shall be cleaned and tuned as part of the alteration work.
1003.2.6 Insulation of Unconditioned Attics
In buildings with three or fewer stories above grade plane, ceiling insulation with a minimum R-value as required by this code shall be installed in accessible attic spaces that are directly above conditioned spaces. For the purposes of this section, accessible attic space is the space between ceiling joists and roof rafters where the vertical clear height from the top of a ceiling joist or the bottom chord of a truss, to the underside of the roof sheathing at the roof ridge, is greater than 24 inches (610 mm). Where the required R-value insulation cannot fit in the attic space, the maximum amount of insulation compatible with available space and existing uses shall be installed.
1003.2.7 Roof Replacement Insulation
For roof replacement on an existing building with insulation entirely above the deck and where the roof slope is less than two units vertical in 12 units horizontal (16-percent slope), the insulation shall conform to the energy conservation requirements for insulation entirely above deck in the International Energy Conservation Code.
Exception: Where the required R-value cannot be provided due to thickness limitations presented by existing rooftop conditions, including heating, ventilating and air-conditioning equipment, low door or glazing heights, parapet heights, proper roof flashing heights, the maximum thickness of insulation compatible with the available space and existing uses shall be installed.
Upcodes Diagrams

Related Code Sections

1003.2 Existing Buildings, Requirements for Alterations
of improvements required by Sections 1003.2.1 through 1003.2.7 shall not be required to exceed 10 percent of the costs of the alterations exclusive of land ...