1101.3.2 Requirements Based on Value of Alterations
Go To Full Code Chapter
Accessible features and construction governed by this chapter shall be provided:
- To the entire building undergoing alterations, as if the building were hereafter erected, where the value of alterations exceeds 50 percent of the value of the existing building.
- To the portion of the building being altered, to the extent of the alteration, including minor alterations but excluding ordinary repairs, where the value of the alteration does not exceed 50 percent of the value of the existing building.
- Within buildings with first occupancies on or before March 13, 1991, bathrooms and powder rooms located in dwelling units in such portion being altered shall comply with this chapter or with prototype layouts established by rule.
Upcodes Diagrams
Related Code Sections
1101.3.2 Accessibility, Requirements Based on Value of Alterations
, as if the building were hereafter erected, where the value of alterations exceeds 50 percent of the value of the existing building.
To the portion of the building ...
1101.3.2 Accessibility, Requirements Based on Value of Alterations
, as if the building were hereafter erected, where the value of alterations exceeds 50 percent of the value of the existing building.
To the portion ...
901.9.4 Fire Protection Systems, Additional Requirements Based on Value of Alterations
If the value of alterations to the building equals ...
901.9.4 Fire Protection Systems, Additional Requirements Based on Value of Alterations
If the value of alterations to the building equals ...
901.9.4.3 Fire Protection Systems, Additional Requirements for Buildings Containing 4 or More Dwelling Units
For buildings containing 4 or more dwelling units, if the value of alterations to an existing space classified in Occupancy Group R-1 or R-2 exceeds ...